Safety Controls; Start-Up And Adjustments; Pressure Switch Tubing Routing - Coleman UGAA075BUJ Installation Manual

High efficiency clam tube heat exchanger series
Table of Contents

Advertisement

288130-UIM-A-0407
CARBON MONOXIDE
POISONING
HAZARD
_WARNING
Failure to follow the steps outlined below for each appliance connected to the venting system being placed into operation could result in carbon
monoxide poisoning or death.
The following steps shall be followed for each appliance connected to the venting system being placed into operation,
while all other appliances
connected to the venting system are not in operation:
1. Inspect the venting system for proper size and horizontal pitch. Determine that there is no blockage, restriction, leakage, corrosion or other
deficiencies,
which could cause an unsafe condition
2. Close all building doors and windows and all doors.
3. Turn on clothes dryers and TURN ON any exhaust fans, such as range hoods and bathroom exhausts, so they shall operate at maximum
speed. Open the fireplace dampers. Do not operate a summer exhaust fan.
4. Follow the lighting instructions.
Place the appliance being inspected in operation. Adjust thermostat so the appliance shall operate contin-
uously.
5. Test each appliance (such as a water heater) equipped with a draft hood for spillage (down-draft or no draft) at the draft hood relief opening
after 5 minutes of main burner operation. Appliances
that do not have draft hoods need to be checked at the vent pipe as close to the
appliance as possible.
Use a combustion analyzer to check the CO2 and CO levels of each appliance. Use a draft gauge to check for a
downdraft or inadequate draft condition.
6. After it has been determined
that each appliance properly vents when tested as outlined above, return doors, windows, exhaust fans, fire-
place dampers and any other gas burning appliance to their normal condition.
7. If improper venting is observed during any of the above tests, a problem exists with either the venting system or the appliance does not
have enough combustion air (Supply Air from outside) to complete combustion. This condition must be corrected before the appliance can
function safely.
NOTE: An unsafe condition exists when the CO reading at the furnace vent exceeds 40 ppm and the draft reading is not in excess of - 0.1 in.
W.C. (-25 kPa) with all of the appliance(s)
operating at the same time.
8. Any corrections
to the venting system and / or to the supply (outside) air system must be in accordance
with the National Fuel Gas Code
Z223.1 or CAN/CGA B149.1-00 Natural Gas and Propane Installation Code (latest editions). If the vent system must be resized, follow the
appropriate
tables in Appendix G of the above codes or for this appliance.
SECTION
Vllh
SAFETY
CONTROLS
CONTROL
CIRCUIT
FUSE
A 3-amp fuse is provided on the control circuit board to protect the 24-
volt transformer
from overload caused by control circuit wiring errors.
This is an ATO 3, automotive
type fuse and is located on the control
board.
BLOWER
DOOR
SAFETY
SWITCH
This unit is equipped with an electrical
interlock switch mounted in the
blower compartment.
This switch interrupts all power at the unit when
the panel covering the blower compartment
is removed.
Electrical supply to this unit is dependent upon the panel that covers the
blower compartment
being in place and properly positioned.
l
CAUTIONI
Main power to the unit must still be interrupted
at the main power
disconnect switch before any service or repair work is to be done to
the unit. Do not rely uoon the interlock switch as a main cower dis-
connect.
Blower
and burner must never
be operated
without
the blower
panel in place.
ROLLOUT
SWITCH
CONTROLS
These controls are mounted on the burner box assembly. If the temper-
ature in the burner box exceeds its set point, the ignition control and the
gas valve are de-energized.
The operation
of this control indicates a
malfunction
in the combustion air blower, heat exchanger or a blocked
vent pipe connection.
Corrective action is required. These are manual
reset controls that must be reset before operation can continue.
PRESSURE
SWITCHES
This furnace is supplied with a pressure switch, which monitors the flow
through the combustion
air/vent piping system.
This switch de-ener-
gizes the ignition control module and the gas valve if any of the follow-
ing conditions are present. Refer to Figure 35 for tubing connections.
1.
Blockage of combustion air piping or terminal.
2.
Blockage of vent piping or terminal.
3.
Failure of combustion air blower motor.
FIGURE 35: Pressure Switch Tubing Routing
LIMIT
CONTROLS
There is high temperature
limit control located on the furnace vestibule
panel near the gas valve. This is an automatic
reset control that pro-
vides over temperature
protection due to reduced airflow, that may be
caused by a dirty filter, or if the indoor fan motor should fail. The control
module will lockout if the limit trips 3 consecutive
times. Control will
reset and try ignition again after 1 hour.
SECTION
IX: START-UP
AND
ADJUSTMENTS
The initial start-up of the furnace
requires the following
additional
procedures:
IMPORTANT: All electrical connections
made in the field and in the fac-
tory should be checked for proper tightness.
When the gas supply is initially connected to the furnace, the gas piping
may be full of air. In order to purge this air, it is recommended
that the
ground union be loosened until the odor of gas is detected. When gas is
detected, immediately
retighten
the union and check for leaks. Allow
five minutes for any gas to dissipate before continuing with the start-up
procedure.
Be sure proper ventilation
is available
to dilute and carry
away any vented gas.
22
Unitary Products Group