VENT TERMINAL
AIR SUPPLY
AREA WHERE
TERMINAL
IS NOT PERMITTED
FIGURE 32: Home Layout
Canadian
Installations I
US Installation 2
A. Clearance above grade, veranda, porch, deck, or balcony
12 inches (30 cm)
12 inches (30 cm)
B. Clearance to window or door that may be opened
12 inches (30 cm)
4 Feet (1.22 m)
C. Clearance to permanently
closed window
12 inches (30 cm)
12 inches (30 cm)
D. Vertical clearance to ventilated soffit located
above the terminal within a horizontal distance
4 Feet (1.22 m)
4 Feet (1.22 m)
of 2 feet (61 cm) from the center line of the terminal
E. Clearance to unventilated soffit
12 Inches (30 cm)
12 Inches (30 cm)
F. Clearance to outside corner
12 Inches (30 cm)
12 Inches (30 cm)
G. Clearance to inside corner
6 Feet (1.83 m)
6 Feet (1.83 m)
3 feet (0.91 m) within a height
3 feet (0.91 m) within a height
H. Clearance to each side of center line extended
15 feet (4.57 m) above the
15 feet (4.57 m) above the
above meter/regulator
assembly
meter/regulator
assembly
meter/regulator
assembly
I. Clearance to service regulator vent outlet
3 feet (0.91 m)
3 feet (0.91 m)
J. Clearance to nonmechanical
air supply inlet to
12 inches (30 cm)
4 Feet (1.22 m)
building or the combustion air inlet to any other appliance
3 feet (0.91 m) above if within
K. Clearance to a mechanical supply inlet
6 feet (1.83 m)
10 feet (3.04 m) horizontally
_. Clearance above paved sidewalk or paved
7 feet (2.13 m) t
7 feet (2.13 m) t
driveway located on public property
M. Clearance under veranda, porch, deck, or balcony
12 inches (30 cm)
12 inches (30 cm)
Vent Termination from any Building Surface
12 inches (30 cm)
12 inches (30 cm)
Above anticipated snow depth
12 inches (30 cm)
12 inches (30 cm)
1. In accordance with the current CSA B149.1-00,
Natural Gas and Propane Installation
Code.
2. In accordance with the current ANSI Z223.1 / NFPA 54, National Gas Code.
1" A vent shall not terminate
directly above a sidewalk or paved driveway
that is located between two single family dwellings
and serves both dwellings.
_: Permitted
only if veranda, porch, deck, or balcony is fully open on a minimum of two sides beneath the floor. For clearance not specified
in ANSI Z223.1 / NFPA
54 or CSA B149.1-00.
Clearance
in accordance
with local installation
codes and the requirements
of the gas supplier and the manufacturer's
Installation
Manual.
Any fresh air or make up inlet for dryer or furnace area is considered
to be forced air inlet.
Avoid areas where condensate
drippage may cause problems such as above planters, patios, or adjacent
to windows where steam may cause fogging.
A terminus of a vent shall be either:
Fitted with a cap in accordance
with the vent manufacturer's
installation
instructions,
or In accordance
with the installation
instructions
for a special venting system.
* Does not apply to multiple installations
of this furnace model. Refer to "VENTING
MULTIPLE UNITS" in this section of these instructions.
IMPORTANT:
Consideration
must be given for degradation
of building materials by flue gases. Sidewall termination
may require sealing or shielding of building surfaces
with a corrosion
resistant material to protect against combustion
product corrosion.
Consideration
must be given to wind direction in order to prevent flue products and/
or condensate
from being blown against the building surfaces. If a metal shield is used it must be a stainless steel material at a minimum dimension
of 20 inches. It is
recommended
that a retaining type collar be used that is attached to the building surface to prevent movement of the vent pipe.
Responsibility
for the provision of proper adequate venting and air supply for application
shall rest with the installer.
Vent shall extend high enough above building, or a neighboring
obstruction,
so that wind from any direction will not create a positive pressure in the vicinity of the vent.
HORIZONTAL
VENT
APPLICATIONS
AND
TERMINATION
When selecting the location for a horizontal combustion air / vent termi-
nation, the following should be considered:
1.
Observe all clearances
listed in vent clearances
in these instruc-
tions.
2.
Termination should be positioned where flue products will not dam-
age plants or shrubs or air conditioning
equipment.
3.
Termination should be located where it will not be affected by wind
gusts, light snow, airborne
leaves or allow recirculation
of flue
gases.
4.
Termination
should be located where it will not be damaged
or
exposed to flying stones, balls, etc.
5.
Termination should be positioned where vent vapors are not objec-
tionable.
6.
Horizontal portions of the vent system must slope upwards and be
supported to prevent sagging. The vent system may be supported
by the use of clamps or hangers secured to a permanent
part of
the structure every 4 ft. (1.22 m).