3. 120 energizing control (digital position detection control)
This control system detects the digital position detection signal and adjusts the rate of acceleration/deceleration accordingly. The motor's induced
voltage waveform is input to the comparator in the form of PWM-switched pulse, and a position detection signal is generated as a reference voltage
which is equal to 1/2 of 370 VDC. However, since there is no induced voltage waveform when the PWM waveform is OFF, the microcomputer works
in an internal processing so that detection is enabled only when it is ON. Based on the position signal detected, actual PWM waveform output timing
is determined. Since it does not use a filter circuit, the accuracy of detection. The microcomputer works in an internal processing to eliminate spiky
voltage during the regenerative process. Furthermore, even if the induced voltage is low, position detection is still possible, and it allows sensor-less
operation at low rotation speed in the initial stage of operation. These reduce the starting current and improve reliability of IPM.
Spiky voltage
(cancelled)
4. 180 energizing control
This is the control system to moderate the speed by the
current phase difference for higher efficiency and lower
noise of the compressor. The current phase difference
control is the control system paid attention to the interre-
lation between efficiency and phase gap generated by
the applied voltage of motor and current in the coil of
motor as shown in the figure below.
This control is the forced magnetization system indepen-
dent of the location of rotor, detecting the phase differ-
ence between driving voltage phase and line current
phase flowing in motor coil, and controls the modulation
rate data to get the phase difference at the best effi-
ciency.
5. DC Current Detection Sensor Circuit
Control of current phase difference is made by reading in the phase difference generated at the both edges of shunt registor (R100) by the compres-
sor electrifying current on the PWB through the Op-amp (IC9) to the microcomputer. This is a control to modulate up to the phase with the best effi-
ciency by comparing the phase of this input current, so called compressor electrifying current, with the compressor driving voltage. In the case that
phase difference between motor voltage and current is large (current delay is large), the control will be made by lowering the compressor modulation
rate data (compressor effective value).
P
FUSE 101
250V 20A
C121
630v
0.33
C119
1000p
Terminal voltage waveform
IPM
N
CIN
Z
R113 18KF
R100
0.02
ZD101
Y
Reference voltage
(1/2 of DC voltage)
Comparator output waveform
(Position signal waveform)
Motor voltage
Motor current
Difference of current
Best timing
and voltage peak
Concept chart of the current phase difference control
TU
TV
TW
R201
100KF
5V
15V
D8
8
-
IC1
1
+
R200
4
1K
C96
IC9
1000P
C97
0.1μ
0V
Inverter current detection circuit
2 – 7
AEX2M14LR
Voltage /Current
phase difference
S
FC1
R
R202
20KF
2
Y
3
Z
R203
2.0KF
5V
R204
200KF
R205
200KF
0V
C