Navien NPE-180A Installation Manual page 19

Condensing water heater
Hide thumbs Also See for NPE-180A:
Table of Contents

Advertisement

Maximum Liquefied Propane Delivery Capacity
in Thousands of BTU/H (0.5" WC Pressure Drop)
Length (including fittings)
Pipe Size
10'
20'
(3m)
(6m)
1/2"
291
200
3/4"
608
418
1"
1,150
787
1 1/4"
2,350
1,620
1 1/2"
3,520
2,420
2"
6,790
4,660
3.3.2 Measuring the Inlet Gas Pressure
WARNING
The water heater cannot function properly without sufficient inlet gas pressure. Measuring the inlet gas pressure should be performed by
a licensed professional only.
The inlet gas pressure must be maintained between 3.5" and 10.5" WC for natural gas and between 8.0" and 13" WC for liquefied propane.
The appliance and its individual shutoff valve must be disconnected from the gas supply piping system during any pressure testing of
that system at test pressures in excess of 1/2 psi (3.5 kPa). The appliance must be isolated from the gas supply piping system by closing its
individual manual shutoff valve during any pressure testing of the gas supply piping system at test pressures equal to or less than 1/2 psi
(3.5 kPa).
To measure the inlet gas pressure:
1. Shut off the manual gas valve on the gas supply line.
18
Installing the Water Heater
30'
40'
50'
(9m)
(12m)
(15m)
160
137
122
336
287
255
632
541
480
1,300
1,110
985
1,940
1,660
1,480
3,750
3,210
2,840
Gas Valve
60'
80'
100'
(18m)
(24m)
(30m)
110
101
94
231
212
197
434
400
372
892
821
763
1,340
1,230
1,140
2,570
2,370
2,200
Opened
Closed
125'
150'
175'
(38m)
(45m)
(53m)
89
84
74
185
175
155
349
330
292
716
677
600
1,070
1,010
899
2,070
1,950
1,730
200'
250'
(60m)
(76m)
67
62
140
129
265
243
543
500
814
749
1,570
1,440