Vertical Through-The-Roof Application & Installation - Majestic fireplaces 360DVS2 Homeowner's Installation And Operating Manual

Multisided top/rear vent convertible direct vent
Table of Contents

Advertisement

Vertical Through-the-Roof Application
This Gas Fireplace has been approved for:
Vertical installations up to 40' (12 m) in height. Up
to a 10' (3 m) horizontal vent run can be installed
within the vent system using a maximum of two 90°
elbows. (Fig. 30)
Max. Height 40'
(12.2m)
Min. Height 8'
(2.4m)
Max. Height
40' (12.2m)
Min. Height
8' (2.4m)
Fig. 30 Support straps for horizontal runs.
max height & length
360DVS
Up to two 45° elbows may be used within the hori-
rev. 9-17-02
zontal run. For each 45° elbow used on the hori-
zontal level the maximum horizontal length must be
reduced by 18" (457 mm).
Example: Maximum horizontal length:
Zero elbows
= 10' (3 m)
1 x 45° elbows = 8¹⁄₂' (2.6 m)
2 x 45° elbows = 7' (2.1 m)
A minimum of an 8 ft. (2.43 m) vertical rise.
Two (2) sets of 45° elbow offsets may be used within
the vertical sections. From zero to max 8 ft. (2.43 m)
vent pipe can be used between elbows. (Fig. 30)
7DVCS supports offsets. (Fig. 33) This application
will require you first determine the roof pitch and use
the appropriate starter kit. See Venting Components
List, Page 22.
The maximum angular variation allowed in the sys-
tem is 270˚. (Fig. 31)
The minimum height of the vent above the highest
point of penetration through the roof is 2' (610mm).
(Fig. 32)
10006326
Max. 10' (3m)
Support Straps
Every 36"
(914mm)
Max. 10' (3m)
FP1443
rjs
360DVS Series Direct Vent Fireplaces
1 + 2 + 3 + 4 = 270°
1
2
3
4
Fig. 31 Maximum elbow usage.
Fig. 32 Maximum termination to roof clearance.
1
2
3
4
FP1444
Min.
2' (610 mm)
FP1185
21