LDVR Series Direct Vent Gas Fireplace

Locating Your Fireplace

E
Y
D
Y
F
Fig. 2 Locate gas fireplace.
A) Flat on wall
B) Cross corner
D) *Room divider
E) *Flat on wall corner
Y) 6" minimum
NOTE: (Fig. 2)
** Island (C) and Room Divider (D) installation is possible as
long as the horizontal portion of the vent system (X) does not
exceed 20' (610cm). See details in Venting Section.
* When you install your fireplace in(D) Room divider or (E)
Flat on wall corner positions (Y), a minimum of 6" (153mm)
clearance must be maintained from the perpendicular wall and
the front side edge of the fireplace.
Refer to (Y) in Figure 2.

Clearance to Combustibles

Top of Unit to Ceiling ............................... 36" (914 mm)
Appliance
Top .......................................................... 0" (0 mm)
Bottom ..................................................... 0" (0 mm)
Side ......................................................... 0" (0 mm)
Back ........................................................ 0" (0 mm)
Venting
Concentric sections of DV Vent
Top, bottom & sides .............................. 1" (25 mm)
Rear Vent Applications:
Top ........................................................ 2" (50 mm)
Sides and Bottom .................................. 1" (25 mm)
Flex Vent .................................................. 7/8" (22 mm)

Mantels

The height that a combustible mantel is fitted above the
fireplace is dependent on the depth of the mantel. This
also applies to the distance between the mantel leg (if
fitted) and the fireplace.
For the correct mounting height and widths refer to
Figs. 3a and 3b, and the following Mantel Charts.
The fitting of a bay window trim kit does not effect
the distances and reference points referred to in the
diagram and chart.
Noncombustible mantels and legs may be installed at
any height and width around the appliance.
When using paint or lacquer to finish the mantel, such
paint or lacquer must be heat resistant to prevent
discoloration.
6
A
B
X
C
X
B
LU584-R
LU584-R
Locating unit
2/23/01 sta
C) **Island
F) Chase installation
A
B
C
CFM146
Mantel Chart
Mantel Shelf
Ref. or Breast Plate Ref.
Depth
V
10"
(254 mm)
A
W
8"
(203 mm)
B
X
6"
(152 mm)
C
Y
4"
(102 mm)
D
Z
2"
(51 mm)
E
Fig. 3a Combustible mantel minimum installation.
Black
Surround
Face
CFM164a
Side of
CFM164a
Combustion Chamber
Mantel Leg Chart
06/22/01 sta
Mantel
Ref.
Leg Depth
F
10" (254 mm)
CFM170
DV Builder Front
G
8" (203 mm)
View
H
6" (152 mm)
I
4" (102 mm)
J
2" (51 mm)
Fig. 3b Combustible mantel leg minimum installation.
V
W
X
Y
Z
3/4" (19 mm) Scribe
Moulding for use with
CFM Cabinets
D
E
Fireplace
Top Louvre
Assembly
Top of Combustion
Chamber
CFM146
Mantel from Top
DV Mantel Chart
7/5/01 sta
of Combustion Chamber
36/39/43 LDVR
33LDVR
17" (432 mm) 16¹⁄₂" (419 mm)
15" (381 mm) 14¹⁄₂" (368 mm)
13" (330 mm) 12¹⁄₂" (318 mm)
11" (279 mm) 10¹⁄₂" (267 mm)
9" (229 mm) 8¹⁄₂" (216 mm)
3/4" (19 mm) Scribe
Moulding for use with
CFM Cabinets
J
I
H
G
Mantel
Leg
K
L
M
N
O
Mantel Leg FromSide
Ref.
of Comb. Opening
K
11¹⁄₂" (292 mm)
L
9¹⁄₂"
(241 mm)
M
7¹⁄₂"
(191 mm)
N
5¹⁄₂"
(140 mm)
O
3¹⁄₂"
(89 mm)
10007317