Condensate Drain; General - Payne PG9MXA Installation, Start-Up, And Operating Instructions Manual

Deluxe 4 ---way multipoise 2 ---stage condensing gas furnace sizes 060 ---120, series a
Hide thumbs Also See for PG9MXA:
Table of Contents

Advertisement

DIRECT VENT (2-PIPE) TERMINATION KIT
2-in. (51 mm) Concentric Vent Kit
3-in. (76 mm)Concentric Vent Kit
2-in. (51 mm)Termination Bracket Kit
3-in. (76 mm) Termination Bracket Kit
Combustion air and vent pipes MUST terminate outside structure.
A factory accessory termination kit must be installed as shown in
Table 14. There are four options of vent/combustion air
termination kits available as shown in Table 14.
NOTE: Combustion air pipe must have the same diameter as
vent pipe.
Concentric Vent/Combustion Air Termination Kit (Direct
Vent/2-Pipe System Only)
Determine an appropriate location for termination kit using the
guidelines provided in section "Vent Termination: General" in
this instruction.
1. Cut one 4-in. (102 mm) diameter hole for 2-in.(51 mm)
kit, or one 5-in. (127 mm) diameter hole for 3-in. (76 mm)
kit.
2. Loosely
assemble
termination components together using instructions in kit.
3. Slide
assembled
kit
through hole.
NOTE: Do not allow insulation or other materials to accumulate
inside of pipe assembly when installing it through hole.
Roof terminations - - Locate assembly through roof to
appropriate height as shown in Fig. 44.
Sidewall terminations - - Locate assembly through
sidewall with rain shield positioned no more than 1-in. (25
mm) from wall as shown in Fig. 44.
4. Disassemble loose pipe fittings. Clean and cement using
same procedures as used for system piping.
5. Check required dimensions as shown in Fig. 44.
Two-Pipe Termination Kit (Direct Vent/2-Pipe System Only)
Determine an appropriate location for termination kit using the
guidelines provided in section "Vent Termination: General" in
this instruction.
1. Cut 2 holes, 1 for each pipe, of appropriate size for pipe
size being used.
2. Loosely install elbow in bracket and place assembly on
combustion-air pipe.
Roof terminations - - Loosely install pipe coupling on
properly cut vent pipe. Coupling must be positioned so
bracket will mount as shown in Fig. 44.
For applications using combustion-air pipe option,
indicated by dashed lines in Fig. 44, install 90° street
elbow into 90° elbow, making a U-fitting. A 180° U-fitting
may be used.
Sidewall terminations - - Install bracket as shown in Fig.
44. For applications using vent pipe option indicated by
dashed lines in Fig. 44, rotate vent elbow 90° from
position shown in Fig. 44.
3. Disassemble loose pipe fittings. Clean and cement using
same procedures as used for system piping.
4. Check required dimensions as shown in Fig. 44.
Multiventing and Vent Terminations
When 2 or more PG9MXA Furnaces are vented near each other,
each furnace must be individually vented. NEVER common vent
or breach vent PG9MXA furnaces.
Table 14 – Vent Termination Kit for Direct Vent/2-Pipe System
TERMINATION SYSTEM
Single Penetration of Wall or Roof
Single Penetration of Wall or Roof
2---Pipe Termination System
2---Pipe Termination System
concentric
vent/combustion
with
rainshield
REMOVED
(Direct Vent/2-Pipe System ONLY) - - When 2 or more PG9MXA
furnaces are vented near each other, 2 vent terminations may be
installed as shown in Fig. 44, but next vent termination must be at
least 36 in. (914 mm) away from first 2 terminations. It is
important that vent terminations be made as shown in Fig. 44 to
avoid recirculation of flue gases.
Step 11 - - Condensate Drain
!
UNIT MAY NOT OPERATE
Failure to follow this caution may result in intermittent
unit operation.
Unit must not be installed, operated, and then turned off and
left in an unoccupied structure during cold weather when
air
temperature drops to 32°F (0°C) and below unless drain trap
and drain line have adequate freeze protection. See Service
and Maintenance Instructions for winterizing procedure.

GENERAL

Condensate trap is shipped installed in the blower shelf and
factory connected for UPFLOW applications. Condensate trap
must be RELOCATED for use in DOWNFLOW and
HORIZONTAL applications.
Condensate trap MUST be used for all applications.
An external trap is not required when connecting the field drain
to this condensate trap.
The field drain connection (condensate trap or drain tube
coupling) is sized for l/2-in. CPVC, 1/2-in. PVC, or 5/8-in. ID
tube connection.
Drain pipe and fittings must conform to ANSI standards and
ASTM D1785, D2466 or D2846. CPVC or PVC cement must
conform to ASTM D2564 or F493. Primer must conform to
ASTM F656. In Canada, use CSA or ULC listed schedule 40
CPVC or PVC drain pipe, fittings, and cement.
When a condensate pump is required, select a pump which is
approved for condensing furnace applications. To avoid
condensate spillage, select a pump with an overflow switch.
Furnace condensate is mildly acidic, typically in the pH range of
3.2 to 4.5. Due to corrosive nature of this condensate, a
condensate pH neutralizing filter may be desired. Check with
local authorities to determine if a pH neutralizer is required.
APPLICATION
The furnace, A/C, and humidifier drains may be combined and
drained together. The A/C drain must have an external,
field-supplied trap prior to the furnace drain connection. All drain
connections (furnace, A/C, or humidifier) must be terminated into
an open or vented drain as close to the respective equipment as
possible to prevent siphoning of the equipment's drain.
See Fig. 46 for example of possible field drain attachment using
1/2-in. CPVC or PVC tee for vent and A/C or humidifier
drain connection.
Outdoor draining of the furnace is permissible if allowed by local
codes. Caution should be taken when freezing. Ambient may
freeze drain pipe and prohibit draining.
46
DIAM. OF COMBUSTION AIR AND VENT
PIPES --- IN (mm)
1, 1---1/2, 2, or 2---1/2 (25, 38, 51, 64 mm)
2---1/2, 3 or 4 (64, 76, 102 mm)
1, 1---1/2 or 2 (25, 38, 51mm)
2---1/2, 3 or 4 (64, 76, 102 mm)
CAUTION

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents