Parameters Mode
The Parameters mode is used to change the parameters on
the drive. To change parameters, perform the following
procedure. See Table 8 for a listing of the VFD parameters
per motor and VFD drive models:
1. Select MENU (SOFT KEY 2). The Main menu will
be displayed.
2. Use the UP or DOWN keys to highlight PARAMET-
ERS on the display screen and press ENTER (SOFT
KEY 2).
3. Use the UP or DOWN keys to highlight the desired
parameter group and press SEL (SOFT KEY 2).
4. Use the UP or DOWN keys to highlight the desired
parameter and press EDIT (SOFT KEY 2).
5. Use the UP or DOWN keys to change the value of the
parameter.
6. Press SAVE (SOFT KEY 2) to store the modified
value. Press CANCEL (SOFT KEY 1) to keep the
previous value. Any modifications that are not saved
will not be changed.
7. Choose another parameter or press EXIT (SOFT KEY
1) to return to the listing of parameter groups. Contin-
ue until all the parameters have been configured and
then press EXIT (SOFT KEY 1) to return to the main
menu.
NOTE:
The current parameter value appears above the
highlight parameter. To view the default parameter value,
press the UP and DOWN keys simultaneously. To restore the
default factory settings, select the Carrier application macro.
Changed Parameters Mode
The Changed Parameters mode is used to view and edit
recently changed parameters on the drive. To view the
changed parameters, perform the following procedure:
1. Select MENU (SOFT KEY 2). The Main menu will
be displayed.
2. Use the UP or DOWN keys to highlight CHANGED
PAR on the display screen and press ENTER (SOFT
KEY 2). A list of the recently changed parameters
will be displayed.
3. Use the UP or DOWN keys to highlight the desired
parameter group and press EDIT (SOFT KEY 2) to
change the parameter if desired.
4. Press EXIT (SOFT KEY 1) to exit the Changed Para-
meters mode.
Drive Parameter Backup Mode
The drive parameter back up mode is used to export the
parameters from one drive to another. The parameters can
be uploaded from a VFD to the removable control panel.
The control panel can then be transferred to another drive
and the parameters downloaded into memory.
Depending on the motor and application, there are two
options available. The first option is to download all
parameters. This copies both application and motor
parameters to the drive from the control panel. This is
recommended when using the same application for drives
of the same size. This can also be used to create a backup
of the parameters group for the drive.
The second option downloads only the application
parameters to the drive. This is recommended when using
the same application for drives of different sizes.
Upload All Parameters —
To upload and store parameters in the control panel from
the VFD, perform the following procedure:
1. Select MENU (SOFT KEY 2). The Main menu will
be displayed.
2. Use the UP or DOWN keys to highlight PAR
BACKUP on the display screen and press ENTER
(SOFT KEY 2).
3. Use the UP or DOWN keys to highlight UPLOAD TO
PANEL and press SEL (SOFT KEY 2).
4. The text "Copying Parameters" will be displayed with
a progress indicator. To stop the process, select
ABORT (SOFT KEY 1).
5. When the upload is complete, the text "Parameter up-
load successful" will be displayed.
6. The display will then return to the PAR BACKUP
menu. Select EXIT (SOFT KEY 1) to return to the
main menu.
7. The control panel can now be disconnected from the
drive.
Download All Parameters —
To download all parameters from the control panel to the
VFD, perform the following procedure:
1. Install the control panel with the correct parameters
onto the VFD.
2. Select MENU (SOFT KEY 2). The Main menu will
be displayed.
3. Use the UP or DOWN keys to highlight PAR
BACKUP on the display screen and press ENTER
(SOFT KEY 2).
4. Use the UP or DOWN keys to highlight DOWNLOAD
TO DRIVE ALL and press SEL (SOFT KEY 2).
5. The text "Restoring Parameters" will be displayed
with a progress indicator. To stop the process, select
ABORT (SOFT KEY 1).
6. When the download is complete, the text "Parameter
download successful" will be displayed.
7. The display will then return to the PAR BACKUP
menu. Select EXIT (SOFT KEY 1) to return to the
main menu.
8. The control panel can now be disconnected from the
drive.