Specifications - Mitsubishi Electric PUHZ-RP250YHA2 Service Manual

Outdoor unit
Hide thumbs Also See for PUHZ-RP250YHA2:
Table of Contents

Advertisement

4

SPECIFICATIONS

Service Ref.
Mode
Power supply (phase, cycle, voltage)
Running current
Max. current
External finish
Refrigerant control
Compressor
Model
Motor output
Starter type
Protection devices
Crankcase heater
Heat exchanger
Fan
Fan(drive)
No.
Fan motor output
Airflow
Defrost method
Noise level
Dimensions
Weight
Refrigerant
Charge
Oil (Model)
Pipe size O.D.
Connection method
Between the indoor &
outdoor unit
A
A
kW
W
kW
/min(L/s)
Cooling
dB
Heating
dB
W
mm(in.)
D
mm(in.)
H
mm(in.)
kg(lbs)
kg(lbs)
L
Liquid
mm(in.)
Gas
mm(in.)
Indoor side
Outdoor side
Height difference
Piping length
PUHZ-RP200YHA2
Cooling
Heating
3 phase 50Hz, 400V
7.70
8.90
19
Munsell 3Y 7.8/1.1
Linear Expansion Valve
ANB52FFJMT
4.7
HP switch
Comp. Shell thermo
Plate fin coil
Propeller fan
0.150 + 0.150
130(2170)
Reverse cycle
58
59
950(37-3/8)
330 + 30(13+1-3/16)
1,350(53-1/8)
135(297)
6.5(14.3)
2.30(FV50S)
9.52(3/8)
25.4(1)
Flared & Brazing
Max. 30m
Max. 120m
8
PUHZ-RP250YHA2
Cooling
9.50
21
Hermetic
5.5
Inverter
HP switch, LP switch
Discharge thermo
2
58
59
136(299)
R410A
7.1(15.7)
1.60(FV50S)
12.7(1/2)
25.4(1)
Flared
Heating
11.1

Hide quick links: