Hydronic piping

Variable speed pump option

Table 6B Recommended Variable Speed Pumps
Model
81
106
151
211
286
*The minimum temperature rise is derived from the chart in FIG. 6-3 with the firing rate and pump speed at 100% as shown in
the table above.
The shaded regions of pump coverage are only available for applications with 230V (60 Hz) supply voltage, all others are
to be 115V. (A field supplied relay is required to connect the 230V pump listed in the shaded area in Table 6B to the boiler
high voltage terminal strip.)
Variable speed pump setup
Before operation, ensure the following:
- Pump is set for an input signal of 0 - 10Vdc by the dip switches on the pump control
- Pump is set for external signal control (if applicable)
- Pump is set for linear output (if applicable)
- If pump does not come equipped with a 0 - 10 Vdc input option, an optional module
will be required from the vendor
Pump sizing and flow requirements are
NOTICE
based on 20 feet of piping, 4 - 90°
elbows, and 2 - fully ported ball valves.
It is required that near boiler piping
NOTICE
systems utilize the Primary/Secondary
configuration shown in FIG. 6-10 only.
The use of other near boiler piping
configurations could result in improper
building and system flow rates leading to
inadvertent boiler high limit shutdowns
and poor system performance.
38
Minimum Temperature Rise*
Grundfos
UP26-96 FC/VS
20.3
22.3
21.2
26.8
26.7
Installation & Operation Manual
Pump
TACO
0013 IFC VS
20.3
21.0
19.8
25.1
24.3
Wilo
Stratos 1.25 3 x 30
21.7
21.5
19.1
23.6
21.9