16.8
MENU SET I
16.8.1

SECONDARY PUMP DELAY

The secondary pump delay parameter sets the length of time the secondary (system) pump will run after a heating
demand has been satisfied. The time range for this parameter is 0 minutes to 40 minutes and is adjustable (in 10
second steps) using the Up or Down buttons. Once the desired time setting has been selected, the Enter/Reset
button should be pressed to store the value. The default pump delay is 30 seconds.
16.8.2

PRIMARY PUMP DELAY

The primary pump delay parameter sets the length of time the primary pump will run after a heating demand has been
satisfied. The time range for this parameter is 0 minutes to 40 minutes and is adjustable (in 10 second steps) using
the Up or Down buttons. Once the desired time setting has been selected, the Enter/Reset button should be
pressed to store the value. The default pump delay is 30 seconds.
16.8.3

DHW PUMP DELAY

The DHW pump delay parameter sets the length of time the DHW pump will run after a hot water demand has been
satisfied. The time range for this parameter is 0 minutes to 40 minutes and is adjustable (in 10 second steps) using
the Up or Down buttons. Once the desired time setting has been selected, the Enter/Reset button should be
pressed to store the value. The default pump delay is 30 seconds.
16.9

MENU SET J SERVICE NOTIFICATION

16.9.1

SERVICE NOTIFICATION IN MONTHS

When the boiler control determines that a scheduled service is due based on days of installation, the display will
alternate the standard display text with the message SERVICE DUE every 5 seconds. This parameter is adjustable
in 1-month intervals using the Up or Down buttons and then stored by pressing the Enter/Reset button. The time
range for this parameter is 0 months to 36 months. The default service interval is 12 months.
16.9.2

SERVICE NOTIFICATION RUNNING HOURS

When the boiler control determines that a scheduled service is due based on the hours of actual operation, the
display will alternate the standard display text with the message SERVICE DUE every 5 seconds. This parameter is
adjustable in 500-hour intervals using the Up or Down buttons and then stored by pressing the Enter/Reset button.
The time range for this parameter is 0 hours to 100,000 hours. The default time is 10,000 hours.
16.9.3

SERVICE NOTIFICATION BOILER CYCLES

When the boiler control determines that a scheduled service is due based on the number of cycles, the display will
alternate the standard display text with the message SERVICE DUE every 5 seconds. This parameter is adjustable
in 500 cycle intervals using the Up or Down buttons and then stored by pressing the Enter/Reset button. The range
for this parameter is 0 cycles to 100,000 cycles. The default is 10,000 cycles.
16.9.4

RESET SERVICE NOTIFICATION COUNTER

Once servicing has been completed, the service notification counter should be reset. Once the menu sub-section has
been accessed, press the Enter/Reset button to reset the service notification counter.
17.0

USER INSTRUCTIONS

Once the installation and commissioning is complete, the equipment owner or their representative should be made
aware of the operation of the appliance and its safety devices. A practical demonstration should be given describing
each functional step. Incorrect use may result in injury and will also invalidate the warranty. The installers guide
should be handed over and kept in a safe place for easy reference. It is strongly recommended that the users read
and understand the separate User and SMART SYSTEM Control Guide
CIRCULATION PUMPS
53