Mitsubishi Electric PUHZ-P200YHA Service Manual page 68

Split-type, heat pump air conditioners
Hide thumbs Also See for PUHZ-P200YHA:
Table of Contents

Advertisement

SW2 setting
Controlling status of compressor
operating frequency
ON
1
2 3 4 5 6
Indoor pipe temperature/Liquid
(TH2(4))
ON
Indoor 4
– 39~88
1
2 3 4 5 6
Indoor pipe temperature/(Cond./Eva.)
(TH5(4))
ON
Indoor 4
– 39~88
1
2 3 4 5 6
Target subcool step
ON
1
2 3 4 5 6
Display detail
Explanation for display
The following code will be a help to know the
operating status of unit.
The tens digit
Display Compressor operating frequency control
1
Primary current control
Secondary current control
2
The ones digit (In this digit, the total number of
activated control is displayed.)
Display Compressor operating frequency control
Preventive control for excessive temp-
1
erature rise of discharge temperature
Preventive control for excessive temp-
2
erature rise of condensing temperature
4
Frosting preventing control
Preventive control for excessive temp-
8
erature rise of radiator panel
(Example)
The following controls are activated.
• Primary current control
• Preventive control for excessive tempe-
rature rise of condensing temperature
• Preventive control for excessive tempe-
rature rise of heatsink
– 39~88
(When the temperature is 0°C or less, "–" and
temperature are displayed by turns.)
– 39~88
(When the temperature is 0°C or less, "–" and
temperature are displayed by turns.)
1~6
68
Unit
Code
display
LED
:
:
Step