Error Indicator (Outdoor) - LG AMNW07GDBL1 Service Manual

Lg multi-inverter type air conditioner svc manual(general)
Hide thumbs Also See for AMNW07GDBL1:
Table of Contents

Advertisement

Part 5. Trouble Shooting

1.3 Error Indicator (Outdoor)

Outdoor Error
Ex) Error 21 (DC Peack)
2 Times
LED01G
(RED)
1 Sec.
1 Time
LED02G
(GREEN)
2 Sec.
Error
Contents
Code
21
DC Link Peak (IPM Fault)
22
CT 2 (Max CT)
DC Link Low Volt.
23
DC Link High Volt.
25
Low Voltage/Over Voltage
26
DC Compressor Position Error
27
PSC/PFC Fault Error
29
COMP Over Current
32
D-Pipe High
35
Low Pressure Error
39
Communication Error
40
CT Sensor (Open/Short)
41
INV. D-Pipe Th Error
43
High Pressure Sensor Error
44
Outdoor Air Th Error
45
Cond. Mid-Pipe Th Error
46
Suction Pipe Th Error
48
Cond. Out-Pipe Th Error
51
Capacity Over
53
Signal Error (Indoor <-> Outdoor)
54
3-Phase Wrong wiring
60
EEPROM Check Sum Error
61
Cond. Pipe Th High
62
Heaksink Th High
65
Heaksink Th Error
67
Outdoor BLDC Fan Lock
73
PFC Fault Error(S/W)
Copyright ©2014 LG Electronics. Inc. All right reserved.
Only for training and service purposes
2 Times
2 Times
1 Sec.
1 Sec.
1 Time
1 Time
2 Sec.
LED01G/M
(Red)
2times ◑ 1times ◑ Over Rated Current
2times ◑ 2times ◑ Input Over Current
2times ◑ 3times ◑
2times ◑ 5times ◑ Abnormal AC Volt Input
2times ◑ 6times ◑ Compressor Starting Fall Error
2times ◑ 7times ◑ Over Inverter PCB input current
2times ◑ 9times ◑ Over Inverter Compressor Current
3times ◑ 2times ◑ D-Pipe Temp. High
3times ◑ 5times ◑ Excessive decrease of Low Pressure
3times ◑ 9times ◑ Communication Error Between PFC
4times ◑
4times ◑ 1times ◑ Open/Short
4times ◑ 3times ◑ Open/Short
4times ◑ 4times ◑ Open/Short
4times ◑ 5times ◑ Open/Short
4times ◑ 6times ◑ Open/Short
4times ◑ 8times ◑ Open/Short
5times ◑ 1times ◑ Over combination
5times ◑ 3times ◑ Communication Poorly
5times ◑ 4times ◑ 3-Phase Wrong Wring of Outdoor Unit
6times ◑
6times ◑ 1times ◑ Cond. Temp. High
6times ◑ 2times ◑ Heatsink Temp. High
6times ◑ 5times ◑ Open/Short
6times ◑ 7times ◑ Outdoor Fan is not operation
7times ◑ 3times ◑ Over Current of Outdoor Unit PFC
LED02G/M
(Green)
DC Link Volt is below 140Vdc
DC Link Volt is above 420Vdc
Micom and INV Micom
CT Circuit Malfunction
(Reverse Phase/Omission of Phase)
Check Sum Mismatching
◑ : A light on the display panel is blink.
- 40 -
case of Error