Vermont Castings BR36 Homeowner's Installation And Operating Manual page 12

Br/bc series woodburning fireplace

Advertisement

BR/BC Series Woodburning Fireplaces
Installing the Chimney System
Start by attaching the first chimney section to the collar on
top of the fireplace.
Install the pipe as pictured in Figure 16. When you get
a good lock, you will hear the pipe clearly snap together.
Once sections are snap-locked in place, it is extremely
difficult to get them apart. Make sure the pipe is firmly
snapped and locked together as each pipe section is
mounted.
When installing elbows, only outer pipe will snap- lock.
Middle pipes simply slide into position. Be sure to always
attach straps on upper elbow to a structural framing mem-
ber. (Fig. 17)
Continue installing the pipe as required until pipe is installed
up through the ceiling. At this point, you must install a
firestop spacer.
Installing the Firestop Spacer
in the Ceiling Hole
A firestop spacer is used to keep pipe spaced properly and
required for safety.
Nail the firestop spacer (at each corner) to the framing
members of the ceiling hole. NOTe: A firestop spacer is
not required at the roof.
Hole sizes listed in Figure 13 for angled firestop spacers
provide minimum required air space to chimney pipe for
ceiling thickness up to 8" (203 mm). When combined
thickness of ceiling material, ceiling joists and flooring
material exceeds 8" (203 mm), adjustments must be made
in framing to assure that minimum air spaces to chimney
are maintained.
Proper Firestop Spacer Installation
Figure 18 shows different installation procedures for both
an area that is an attic and an area that is not an attic.
If the area above the ceiling is not an attic, position
the firestop spacer with the
flange on the ceiling side and
the angled portion extending
up into the hole.
If the area above the ceiling is
an attic, position the firestop
spacer with the flange on the
top of the framed hole and
the angled portion extending
down into the hole.
Firestop spacers are not
available for nor are they
required on vertical walls.
12
Attic Installation
NOTe: If the attic insulation shield is used, the
firestop is not required in the attic installation.
Fig. 18 Installing firestop spacer.
Pipe Section
Fig. 16 Install pipe, listening for the snap-lock to fasten.
FP558
BR
11/10/97
elbow Strap
Angled Strap
Fig. 17 Attach straps to a structural framing member.
Ceiling Installation
Nails (4)
Firestop
Spacer
Joist
FP593
SR/C
11/20/97
Pipe
Rim
Hem
Lance
Pipe
Rim
FP558
Support Structure
Elbow Strap
(must be tight)
Ceiling Hole
Framing
Angled Firestop
Chimney Support Strap
(must be tight)
FP270/271
FP270/271
CR Series
2/19/99 djt
Joist
Firestop
Spacer
Nails (4)
FP593
7412944