A-9
CONNECTION OF RANGER® 305LPG TO PREMISES
240 Volt
60 Hz.
3-Wire
Service
DOUBLE POLE DOUBLE THROW
SWITCH RATING TO BE THE SAME
AS OR GREATER THAN PREMISES
SERVICE OVERCURRENT
PROTECTION.
50 AMP, 120/240
VOLT PLUG
NEMA TYPE 14-50
• Only a licensed, certified, trained electrician should install the machine to a premises or residential
electrical system. be certain that:
• The installation complies with the National Electrical Code and all other applicable electrical codes.
• The premises is isolated and no feedback into the utility system can occur. Certain state and local
laws require the premises to be isolated before the Generator is linked to the premises. Check your
state and local requirements.
240 VOLT
240 VOLT
SWITCH RATING TO BE THE SAME
AS OR GREATER THAN PREMISES
PROTECTION.
SERVICE OVERCURRENT
VOLT PLUG
50 AMP, 120/240
120 VOLT
COMPANY
Service
POWER
60 Hz.
3-Wire
NEMA TYPE 14-50
240 Volt
METER
DOUBLE POLE DOUBLE THROW
N
PROTECTION
POLE
DOUBLE
240 VOLT
GROUNDED CONDUCTOR
SERVICE
OVERCURRENT
PREMISES
DISCONNECT AND
BUS
GROUND
CIRCUIT
NEUTRAL
BREAKER
120 VOLT
40AMP
LOAD
RECEPTACLE
50 AMP, 120/240 VOLT
GND
N
NOTE: No. 6 COPPER CONDUCTOR CABLE SEE
NATIONAL ELECTRICAL CODE FOR ALTERNATE WIRE
SIZE RECOMMENDATIONS.
• A double pole, double throw transfer switch in conjunction with the properly rated double throw
circuit breaker is connected between the generator power and the utility meter.
INSTALLATION
240 VOLT
POWER
COMPANY
120 VOLT
METER
240 VOLT
50 AMP, 120/240 VOLT
RECEPTACLE
120 VOLT
40AMP
240 VOLT
DOUBLE
POLE
CIRCUIT
BREAKER
GND
N
WARNING
RANGER® 305LPG
GROUNDED CONDUCTOR
NEUTRAL
BUS
DISCONNECT AND
GROUND
NOTE: No. 6 COPPER CONDUCTOR CABLE SEE
NATIONAL ELECTRICAL CODE FOR ALTERNATE WIRE
SIZE RECOMMENDATIONS.
A-9
N
LOAD
PREMISES
SERVICE
OVERCURRENT
PROTECTION