11

REFRIGERANT PIPING TASKS

11-1. REFRIGERANT PIPING SYSTEM
Line-Branch Method
Connection Examples
(Connecting to 4 Indoor Units)
Total Piping Length
Permissible
Farthest Piping Length
Length
Farthest Piping Length After First Branch
High/Low Difference in Indoor/Outdoor Section
Permissible High/
Low Difference
High/Low Difference in Indoor/Indoor Section
Selecting the Refrigerant Branch Kit
Select Each Section of Refrigerant Piping
(1) Section From Outdoor Unit
to First Branch (A)
(2) Sections From Branch to
Indoor Unit (a,b,c,d)
(3) Section From Branch to
Branch (B,C)
Select the size from the table to the right.
Additional refrigerant charge
• Refrigerant of 3kg equivalent to 50m total
extended piping length is already included
when the outdoor unit is shipped.
Thus, if the total extended piping length is
50m or less, there is no need to charge with
additional refrigerant.
• If the total extended piping length exceeds
50m, calculate the required additional
refrigerant charge using the procedure
shown on the right.
• If the calculated additional refrigerant charge
is a negative amount, do not charge with any
refrigerant.
A
A+B+C+a+b+c+d
(L)
A+B+C+d
80m
( )
B+C+d
30m
(H)
30 meters or less (If the outdoor unit is lower, 20 meters or less)
(h)
12 meters or less
Use an optional branch piping kit (CMY-Y62-G-E).
(1) Refrigerant Piping Diameter In Section
From Outdoor Unit to First Branch
(Outdoor Unit Piping Diameter)
Model
Each
Section of
PUMY-P100~140
Piping
(3) Refrigerant Piping Diameter In Section
From Branch to Branch
Liquid Line (mm)
9.52
<Additional Charge>
Additional
refrigerant charge
<Example> Outdoor model : 125
Indoor 1 : 63
2 : 40
3 : 25
4 : 20
The total length of each liquid line is as follows;
9.52 : A + B + C + a = 10 + 10 + 10 + 15 = 45m
6.35 : b + c + d = 10 +10 + 20 = 40m
<Calculation example>
Additional
refrigerant charge = 45
B
C
a
b
c
120m
Piping Diameter (mm)
Liquid Line
9.52
Gas Line
15.88
Gas Line (mm)
15.88
Liquid pipe size
Total length of
9.52 × 0.06
=
+
(kg)
(m) × 0.06 (kg/m)
A :
9.52 10m
a : 9.52
B :
9.52 10m
b : 6.35
C :
9.52 10m
c : 6.35
d : 6.35
0.06 + 40
0.024 – 3.0 = 0.7kg (rounded up)
×
×
77
L
d
A
Outdoor Unit
B
First Branch
C
Indoor unit
(2) Refrigerant Piping Diameter In Section
From Branch to Indoor Unit
(Indoor Unit Piping Diameter)
Model number
Piping Diameter (mm)
Liquid Line
50 or lower
Gas Line
Liquid Line
63 to 140
Gas Line
Liquid pipe size
Refrigerant
Total length of
amount for outdoor
6.35 × 0.024
unit
(m) × 0.024 (kg/m)
15m
10m
At the conditions
below:
10m
20m
6.35
12.7
9.52
15.88
3.0kg

Hide quick links: