Mitsubishi PUMY-P100YHM Technical & Service Manual page 55

Table of Contents

Advertisement

9-5. INTERNAL SWITCH FUNCTION TABLE
PUMY-P100YHM
PUMY-P100YHM1
PUMY-P100YHMA
PUMY-P100YHMA-BS
Switch
Step
SW U1
1st digit
SW U2
2nd digit
SW1 Digital
Display
1~8
Switching
1
Selects operating system startup
Connection Information Clear Switch
2
Abnormal data clear switch input
3
SW2
Function
Pump down
4
Switching
5
Auto change over from Remote controller
6
1
ON/ OFF from outdoor unit
SW3 Trial
operation
2
Mode setting
SW4
Model
1~6
Switching
1
Pressure limitation value change
Change the indoor unit's LEV opening at
2
start
Fixing the indoor units linear expansion
3
SW5
valve opening
Function
Fix the operation frequency
4
switching
Change the indoor unit's LEV opening
5
at defrost
Switching the target sub cool.
6
During the FAN or COOL mode,and thermo-OFF
7
or OFF in heating operation, set the opening of
linear expansion valve on indoor unit 1
During the FAN or COOL mode,and thermo-OFF
8
in heating operation, set the opening of linear ex-
pansion valve on indoor unit 2
1 SW5-7 Refrigerant amount shortage measure during heating operation
(Refrigerant piping is long etc.)
2 SW5-8 Countermeasure against room temperature rise for indoor unit in FAN, COOL, and thermo-OFF (heating) mode.
PUMY-P125YHM
PUMY-P125YHM1
PUMY-P125YHMA
PUMY-P125YHMA-BS
Function
0
SWU2
(2nd digit)
ON
OFF
1
2 3 4 5 6 7 8
1 MODEL SELECT 1:ON 0:OFF
SW4
MODELS
1 2 3 4 5 6
1 1 0 0 1 0
PUMY-P100
1 1 0 0 0 1
PUMY-P125
1 1 0 0 1 1
PUMY-P140
PUMY-P140YHM
PUMY-P140YHM1
PUMY-P140YHMA
PUMY-P140YHMA-BS
Operation in Each Switch Setting
ON
OFF
0
SWU1
(1st digit)
With centralized
Without centralized
controller
controller
Clear
Do not clear
Clear abnormal data
Normal
Normal
Run adjustment mode
Disable
Enable
ON
OFF
Heating
Cooling
Normal
Enable
Enable
Normal
Fix
Normal
Fix
Normal
Enable
Normal
Enable
Normal
Active
Inactive
Active
Inactive
55
When to Set
<Initial settings>
0
Before turning
the power on
SWU2
(2nd digit)
Can be set
<Initial settings>
either during
ON
operation or not.
OFF
1
<Initial settings>
Before turning the
power on
ON
OFF to ON any time after
the power is turned on.
OFF
During compressor
1
running
Before turning the
power on
<Initial settings>
Any time after the
power is turned on.
<Initial settings>
Set for each capacity.
Before the power
is turned on.
<Initial settings>
Can be set when off
or during operation
ON
OFF
1
OFF to ON during com-
pressor running.
Can be set when off
or during operation
Remarks
0
SWU1
(1st digit)
2 3 4 5 6 7 8
2 3 4 5 6
ON
OFF
1
2
2 3 4 5 6 7 8