BV4536, BV5142 Natural Vent Gas Fireplace
VERTICAL VENTING WITH TWO (2)
45° ELBOWS
A
B

INSTALL VENT COMPONENTS

FP1294
1. Attach the first piece of vent piping (elbows or straight pipe)
vert vent w elbows
to the pipe connector located above the fireplace. Secure
first section of pipe to damper collar with three (3) screws.
2. Continue to add vent components. Be certain that each
section is locked properly.
3. Where necessary, add support brackets. Figure 9. Incline
runs must be supported every 3'. Vertical runs must be sup-
ported every 8', using wall straps. Slip wall straps loosely
on to pipe. Attach straps to framing members using nails or
screws. Tighten nut/bolt to secure pipe.
Always maintain minimum clearances
around vent systems. The minimum
clearances to combustibles is 1" around
vent pipe. For ceiling firestops and verti-
cal sections of vent pipe a 1" minimum
clearance all around the pipe must be
maintained. Do not pack the open air
spaces with insulation or other materials.
This could cause high temperatures and
may present a fire hazard.
12
NOTE: A and B must satisfy this
condition:
A + B < 40' Maximum
A + B > 14' Minimum
Figure 8 -
Vertical Venting with Two
(2) 45° Elbows
FP2194
VENT INSTALLATION
Never use more than two (2) 45° elbows.
When using adjustable elbows, never
exceed 45°.
Wall Studs
FP2195
Figure 9 -
Install Pipe Supports
Wall Strap
Vent Pipe
41D2001