Operation - Smith 88 Installation And Operation Instructions Manual

Gas-fired residental steam gsx boilers
Table of Contents

Advertisement

B. OPERATION
1. Assure that the gas supply pressure to the boiler is
regulated to 1/2 psi or less (approx. 13.5 inches of
water).
2. Install a service valve, sediment trap, and ground
joint union at the gas supply connection as shown in
Figure 5.1.
CAUTION
Use a pipe joint sealing compound that is resistant to
the action of liquefied petroleum gas. A non-resistant
compound may lose sealing ability in the presence of
this gas, resulting in a gas leak and fire or explosion
potential.
3. Check piping for leaks. Use an approved gas
detector or a non-corrosive leak detection fluid. If
leaks are found, turn off all gas supply to the
appliance and repair as necessary.
4. The boiler and its individual shut off valve must be
disconnected from the gas supply piping system
during any pressure testing of that system at test
pressures in excess of 1/2 psi (3.5kPa).
The boiler must be isolated from the gas supply
piping system by closing its individual manual shut
off valve during any pressure testing of the gas
supply piping system at test pressures equal to or less
than 1/2 psi (3.5 kPa).
CAUTION
Do not subject the boiler gas valve to pressure in
excess of 1/2 psi (3.5 kPa). Doing so may damage the
valve.
Figure 5.1
INSTALLATION AND OPERATING INSTRUCTIONS
5. Refer to table 5.4 for minimum supply pressure for
the purpose of input adjustment.
Table 5.4: Minimum Supply
Pressure Natural Gas
Model
88
118
147
177
206
236
288
6. Install the boiler such that the gas ignition system
components are protected from water (dripping,
spraying, rain, etc.) during appliance operation and
service (circulator replacement, condensate trap
clean out, control replacement, etc.)
7. The boiler and its gas connection must be leak tested
before placing the boiler in operation.
8. Typical gas train manifold is illustrated in Figure 5.2.
Figure 5.2: Gas Train Manifold
Supply
Pressure
(in. Water)
5.00
5.00
5.00
5.35
5.00
5.00
5.56
11

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

118147177206236288

Table of Contents