Boiler Data; Fault Finding - Potterton Flamingo RS40 Installation And Service Manual

Balanced flue gas fired boiler
Table of Contents

Advertisement

2. Pull off the lead at the generator, then unclip the lead from the two clips beneath the combustion
chamber.
3. Replacement is the reverse of removal.
CAUTION: When fitting the replacement lead, ensure that the end with the clear insulation is connected to
the electrode and that with the black insulation connected to the generator.
4. Test the boiler as described in

BOILER DATA

Information concerning Boiler setting data can be found in

8. FAULT FINDING

As well as the fault finding chart given, reference should also be made to the wiring diagrams
electrical faults check Figures 15,
Instruction for Gas Multi-meter booklet.
CONDITION
A. Pilot fails to light.
Page 19
Service Section – Page 20
CONDITION
6, 'Final Adjustment'
16
and 17. Electrical procedures described are in accordance with the
POSSIBLE CAUSE
(1) No gas supply.
(2) Control button not pressed
fully down.
(3) Blocked pilot filter
POSSIBLE CAUSE
4) Blocked pilot injector.
Table
1.
REMEDY
Check all cocks are open in
the supply to the boiler.
Control button must be
pressed fully down.
(a) Remove plastic electrical
terminal cover from top of gas
control valve by unscrewing
the screw.
(b) Remove the four screws
securing the solenoid valve to
the top of the control valve.
(c) Lift off the solenoid valve
and the gasket beneath.
REMEDY
(d) Unscrew and remove the
single screw securing the flat
plate to the main valve body,
then lift off the plate and the
gasket beneath.
(e) Lift out the filter and
replace as necessary.
(f) Re-assemble in the reverse
order.
Remove and change the
injector as described in
Maintenance Instructions
Section 7.b.
Figure
6. For