Figure 15 - Flashing Installation
Storm Collar Installation (SC1)
Place storm collar over pipe and slide down
until it is snug against open edge of flash-
ing (see Figure 16). Use SC1 for all round
terminations. Apply waterproof caulk around
perimeter of collar to provide a proper seal.
Chimney
Pipe
Storm
Collar
Figure 16 - Storm Collar
Terminations/Spark Arrestor
Fireplace system must be terminated with
listed round top or chase terminations. In any
case, refer to installation instructions supplied
with termination. Terminations approved for
this fireplace are RT-8DM, RTL -8DM and
RLT-8DM that can be used for flashing or
chase and ET-8DM, ETO-8DM, ETL-8DM
and ETLO-8DM for chase style termination
only. Figure 17 shows an RTL-8DM round
top termination.
CAUTION: Do not seal open-
ings on the rooftop flashing. Fol-
low the installation instructions
provided with the termination
being used.
109034-01M
VENTING INSTALLATION
Continued
Overlap
Shingles Top
and Sides Only
Waterproof
Caulk
Flashing
www.fmiproducts.com
Terminations with 16" slip pipe sections are
available. RTT-8DM, RTTL-8DM and RLTT-
8DM are approved for flashing installations.
When needed, these adjustable terminations
may be used in combination with pipe assem-
bly to achieve correct chimney height.
Note: In the rare instance there is a problem
with side driven rain or wind or chimney is
not drafting properly, an ADS-8DM (Anti-Draft
Shield) can be used with round terminations.
RTL-8DM
Attach Bracket
Tabs to
Outer Pipe
(3 Places)
Secure with
Screws
Overlap
Shingles Top
and Sides
Figure 17 - Termination
CHASE INSTALLATIONS
Instructions for chase installations are includ-
ed with chase style termination chosen. In a
multiple chase installation, be sure to provide
adequate distance between terminations to
prevent smoke spillage from one termination
to another. We suggest that terminations be
separated at least 24", center to center and
stacked at a vertical height difference of 18"
(see Figure 18, page 12).
Note: If a decorative shroud is to be installed,
contact manufacturer for specifications.
Level of Flue
Gas Outlet
Flue Pipe of
RTL-8DM
Inside Inner
Pipe of
Chimney
Caulk
Collar
Flashing
Underlap Shingles
Bottom Only
11