Operation - Liebert GXT User Manual

1800-2700 va 208v
Hide thumbs Also See for GXT:
Table of Contents

Advertisement

UPS On Indicator (Green)
The UPS On indicator is illuminated when the UPS inverter is operating and
supplying power to your connected loads.
Battery Indicator (Amber)
The Battery indicator is illuminated when the UPS is operating from the battery
system.
AC Input Indicator (Green)
The AC Input indicator is illuminated when utility power is available and within the
input specification.
Output Voltage Selector Switches
The Output Voltage Selector Switches, located on the rear of the UPS, are
designed to allow selecting or changing the desired output voltage to match the
utility. The settings to choose from are 208, 220, 230, and 240 VAC output. The
factory default setting is 208 VAC.
NOTE:
Never change the switch settings while UPS is on and powering
connected loads.
Switch positions for voltages:
208 VAC
220 VAC
own
230 VAC
240 VAC
NOTE:
Setting output voltage to any other voltage than 208 VAC will
automatically increase the 1800 VA UPS VA and Watt rating to 2000 VA/1400W
and the 2700 VA UPS VA and Watt rating to 3000 VA/2100W.

OPERATION

NORMAL MODE OPERATION
During normal operation, utility power provides energy to the UPS. The filters,
the power factor conditioning circuit and the inverter process this power to
provide computer grade power to connected loads. The UPS maintains the
batteries in a fully charged state.
The four green LEDs indicate an approximate level of load in 25% increments. If
the UPS becomes loaded beyond full rating, the fifth (amber) LED indicator will
illuminate and sound an alarm.
The display template indicates the percentage of load on the UPS output. Figure
1 displays approximately 51-75% loading.
11

Advertisement

Table of Contents
loading

Table of Contents