Remote Emergency Power Off; Figure 48 Emergency Power Off - Liebert 610 Series Operation & Maintenance Manual

100-1000kva, 60hz three phase single-module
Hide thumbs Also See for 610 Series:
Table of Contents

Advertisement

3.3.7

Remote Emergency Power Off

The Remote Emergency Power Off (REPO) mode is used to remove all power from the critical load.
The Remote Emergency Power Off control is a user-provided switch located remotely from the UPS
system. It will normally be in the same room as the critical load equipment. This mode can also be ini-
tiated by an automatic contact closure in the same external circuit as the manually operated switch.
When you operate the Remote Emergency Power Off switch, all UPS circuit breakers are opened,
including the bypass circuit breaker. All power through the UPS is removed from the load. Typically,
the REPO circuit also opens the circuit breakers that provide power to the bypass lines and the UPS
controls.
Refer to 3.4.4 - Shutdown Procedures.

Figure 48 Emergency power off

BFB
RIB
MAIN INPUT
SWITCHGEAR
THREE BREAKER MAINTENANCE BYPASS SWITCHBOARD
MBB
BIB
UPS MODULE
Static
Switch
Disconnects
CONTROL POWER
Controls
Rectifier/
Charger
INPUT
CB
65
Static
Bypass
Switch
Bypass CB
Inverter
OUTPUT
CB
Battery
MBD
Operation
Critical
Load
AC Output
MIB