Battery Run Times - Liebert 500-650 VA User Manual

500-650 va 230v
Table of Contents

Advertisement

ENVIRONMENTAL
Operating Temperature
Storage Temperature
Relative Humidity
Operating Elevation
Audible Noise
AGENCY
Safety
Surge
ESD
Susceptibility
Electrical Fast Transient/
Burst
Emissions
Harmonics
Conducted Immunity
Flicker
Transportation

Battery Run Times

Note: Approximate discharge times are in minutes and
at 25°C (77°F) with resistive load.
Up to 3000 m (10,000 ft.) at 35°C (95°F) w/o derating
EN50091-1-1, TUV/GS listed, CE Compliance Mark
Load %
5
10
20
30
40
50
60
70
80
90
100
0°C to +40°C (+32°F to + 104°F)
-15°C to +50°C (+5°F to + 122°F)
0% to 95%, non-condensing
< 40 dBA, at 1 meter
EN61000-4-5, Level 3, Criteria A
EN61000-4-2, Level 3, Criteria A
EN61000-4-3, Level 2, Criteria A
EN61000-4-4, Level 3, Criteria A
EN50091-2, Class B
EN61000-3-2
EN61000-4-6
EN61000-3-3
ISTA Procedure 1A
500VA
95
53
25
19
12
8
7
5
3
3
2
18
650VA
117
73
35
20
12
8
7
4
3
2
1