Operation Range; Installation Site - Daikin FAQ100BUV1B Operation Manual

Split system wall mounted type
Hide thumbs Also See for FAQ100BUV1B:
Table of Contents

Advertisement

Do not operate the air conditioner with a wet
hand.
An electric shock may result.
Do not place items that might be damaged by
water under the indoor unit.
Water may condensate and drip if the humidity
reaches 80% or if the drain exit gets clogged.
Do not place a burner or heater at a place
directly exposed to the wind from the air con-
ditioner.
Incomplete combustion of the burner or heater
may result.
Do not allow a child to mount on the outdoor
unit or avoid placing any object on it.
Falling or tumbling may result in injury.
Do not expose animals and plants directly to
the wind.
Adverse influence to animals and plants may
result.
Do not wash the air conditioner with water.
Electric shock or fire may result.
Do not install the air conditioner at any place
where flammable gas may leak out.
If the gas leaks out and stays around the air con-
ditioner, a fire may break out.
Execute complete drain piping for perfect
drainage.
Incomplete piping may result in a water leakage.
The appliance is not intended for use by
young children or infirm persons without
supervision.
Young children should be supervised to
ensure that they do not play with the appliance.
Consult with installation contractor for
cleaning the inside of the air conditioner.
Wrong cleaning may make the plastics parts
broken or cause failure of water leakage or elec-
tric shock.
Do not touch the air inlet or aluminium fin of
the air conditioner.
Otherwise, injury may be caused.
Do not place objects in direct proximity of
the outdoor unit and do not let leaves and
other debris accumulate around the unit.
Leaves are a hotbed for small animals which can
enter the unit. Once in the unit, such animals can
cause malfunctions, smoke or fire when making
contact with electrical parts.

3. OPERATION RANGE

If the temperature or the humidity is beyond the fol-
lowing conditions, safety devices may work and the
air conditioner may not operate, or sometimes,
water may drop from the indoor unit.
3
COOLING
INDOOR
OUTDOOR
TEMPERA-
UNIT
TURE
DB
18 to 37
RZQ100
WB 12 to 28
DB
18 to 37
RQ100
WB 12 to 28
DB
18 to 37
RR100
WB 12 to 28
HEATING
INDOOR
OUTDOOR UNIT
TEMPERATURE
RZQ100
DB
10 to 27
RQ100
DB
10 to 27
D B: Dry bulb temperature
WB: Wet bulb temperature
The setting temperature range of the remote con-
troller is 16°C to 32°C.

4. INSTALLATION SITE

Regarding places for installation
• Is the air conditioner installed at a well-ventilated
place where there are no obstacles around?
• Do not use the air conditioner in the following
places.
a.Filled with much mineral oil such as cutting oil
b.Where there is much salt such as a beach area
c.Where sulfured gas exists such as a hot-spring
resort
d.Where there are considerable voltage fluctua-
tions such as a factory or plant
e.Vehicles and vessels
f .Where there is much spray of oil and vapor such
as a cookery, etc.
g.Where there are machines generating electro-
magnetic waves
h.Filled with acid and/or alkaline steam or vapor
• Is a snow protection measure taken?
For details, consult your dealer.
Regarding wiring
• All wiring must be performed by an authorized
electrician.
To do wiring, ask your dealer. Never do it by yourself.
• Make sure that a separate power supply cir-
cuit is provided for this air conditioner and
that all electrical work is carried out by quali-
fied personnel according to local laws and
regulations.
OUTDOOR
TEMPERA-
HUMIDITY
TURE
80% or
DB – 15 to 50
below
80% or
DB
– 5 to 46
below
80% or
DB – 15 to 46
below
OUTDOOR
TEMPERATURE
DB
–19.5 to 21
WB
– 20 to 15.5
DB
– 9 to 21
WB
– 10 to 15
English