SecTiON iii – iNSTALLATiON iNSTRUcTiONS (continued)
recommended boiler pipinG for
combinaTion heaTinG & coolinG sysTems
There are many possible causes of oxygen
contamination such as:
1. Addition of excessive make-up water as a result of
system leaks.
2. Absorption through open tanks and fittings.
3. Oxygen permeable materials in the distribution
system.
In order to insure long product life, oxygen sources
should be eliminated. This can be accomplished by
taking the following measures:
insTallaTion of JackeT supporT
brackeTs To base end panels
22
fiG. 17
fiG. 18
1. Repairing system leaks to eliminate the need for
addition of make-up water.
2. Eliminating open tanks from the system.
3. Eliminating and/or repairing fittings which allow
oxygen absorption.
4. Use of non-permeable materials in the distribution
system.
5. Isolating the boiler from the system water by
installing a heat exchanger.
Open Jacket Parts Carton
15.
INSTALLATION OF JACKET PARTS COMMON TO
ALL BOILER SIZES
1. Attach Lower Jacket End Panel Support Bracket to
Base End Panel (Both ends) using ¼"-20 x ½" self-
tapping screws, see Fig. 2 and 18.
2. Attach Lower Left and Lower Right Jacket End
Panels to their respective brackets using #10-32 x
½" self-tapping screws, see Fig. 19.
3. See Fig. 7 "Purpose of Tappings and Their
Location" and remove necessary knockouts from
Upper Left and from Upper Right Jacket End
Panels.
4. Place Upper Right End Panel on top of Lower
Right End Panel with lip on bottom of Upper Panel
positioned behind Lower Panel. Secure to section
using #10-32 x ½" self-tapping screws. Attach
Upper Left End Panel in a similar manner, see Fig.
19.
NOTE: FOR INSTALLATION OF THE
FRAMEWORK FOR THE LOWER UNCOMMON
JACKET PARTS REFER TO THE FOLLOWING:
a. 5006B thru 5010B section boilers – Paragraph
16, Fig. 21
b. 5011B thru 5026B section boilers – Paragraph
30, Fig. 24, 25 or 26
COMPLETION OF JACKET INSTALLATION –
5006B THRU 5010B SECTION BOILERS
NOTE: Do not tighten any screws until Jacket
installation is complete.
INSTALLATION OF LOWER FRAMEWORK
16.
With "U" channel facing down, slip upper front channel
behind joints formed by End Panels and secure to End
Panels using #8 SMS. Position Lower Front Channel
so that "U" of channel faces boiler. Slip Lower Front
Channel behind Lower End Panels and secure with
#8 SMS. Repeat similar procedure for installation of
Upper Rear and Lower Rear Channels.
17.
INSTALLATION OF VESTIBULE PANEL refer to
Fig. 20.