13.1 single gas valve Models (Fs 90 - 105) Figure 14a
Proceed as follows to adjust the single gas valve:
Insert the flue analysis probe into the flue sampling hole as instructed in section 17 (figure 17).
Press and hold the
appear on the display in the position shown in figures 15a and 15b
mode'.
Press the
key to set the maximum heat output, with the display showing 100% (figure 15a).
caution: in the event of the boiler failing to ignite, or when replacing the gas valve, the recommended
procedure is to tighten the adjuster screw (v) fully and then back off 3 turns, repeating the steps
described above.
Turn the adjuster screw V on the gas valve until you achieve the CO
gas (G20) and in table 2.2 for propane (LPG):
-
Turn the screw anti-clockwise to increase the CO
-
Turn the screw clockwise to decrease the CO
Press the
key to set the minimum heat output, with the display showing 0% (figure 13b).
Turn the adjuster screw K on the gas valve until you achieve the CO
-
Turn the screw clockwise to increase the CO
-
Turn the screw anti-clockwise to decrease the CO
13.2 double gas valve Models (Fs 130 - 160) Figure 14b
Proceed as follows to adjust the double gas valve:
• Connect a pressure gauge to the P1OUT pressure measurement hole on valve 1.
• Insert the probe of the flue gas analyzer in the sampling port as indicated in heading 17 - figure 17.
• Switch on the boiler, activating the "setting function" from the control panel by pressing and holding the
and
keys simultaneously until the
15a and 15b
. You are now in 'calibration mode'.
• Press the
key to set the maximum heat output, with the display showing 100% (figure 15a).
caution: in the event of the boiler failing to ignite, or when replacing the gas valves, the recommended
procedure is to tighten the adjuster screws (v1) and (v2) fully and then, depending on the model, back
off 2¼ turns (Fs 130) or 2½ turns (Fs 160), repeating the steps described above.
• Turn both gas valve adjuster screws (V1) and (V2) so as to set the CO
natural gas (G20) and in table 2.2 for propane (LPG):
-
Turn the screw clockwise to decrease the CO
-
Turn the screw anti-clockwise to increase the CO
Press the
key to set the minimum heat output, with the display showing 0% (figure 15b).
• Turn the adjuster screw K1 of gas valve 1 so as to set the pressure value (Pout) as indicated in table 2.1
for natural gas (G20) and in table 2.2 for propane (LPG):
c.
Turn the screw clockwise to increase pressure (CO
InstructIons pertaInInG to the InstaLLer
and
keys on the control panel simultaneously for 7 seconds until the
symbols are displayed, positioned as illustrated in figures
levels shown in table 2.1 for natural
2
level.
2
level.
2
levels shown in table 2:
2
level.
2
level.
2
values as indicated in table 2.1 for
2
level.
2
level.
2
increasing).
2
30
symbols
. You are now in 'calibration
912.823.1 - GB