Troubleshooting CH04
Display
Title
code
Drain pump
04
/ Float switch
Check Point
1. Check the wire connection. (Open, Soldered poorly) ¡ Repair the connection or change the PCB.
2. Check the resistance of float switch (Abnormal : Open, Normal : short) ¡ Check the float switch.
3. Check the level of water
4. Check the volt. Of Drain pump power supply. (AC 230V) ¡ Repair or Change the main PCB.
Cause of error
• Float switch Open.
(Normal : short)
CN Float
0
Check the resistance
Troubleshooting Guide
Check point & Normal condition
• The connection of wire(Drain pump/ Float switch)
• Drain pump power input. (220V)
• Drain tube installation.
• Indoor unit installation. (Inclination)
Service Manual 41