Gas Piping Installation - American Standard YCY024G1L Installation Operation & Maintenance

Single package gas/electric 14 seer convertible 2 - 5 ton
Table of Contents

Advertisement

IMPORTANT: Before making the gas pipe connection give
serious consideration to providing the required clearance nec-
essary to remove the access panels on the unit
(e.g., economizer and filter access panels).
NOTE: In the absence of local codes, the installation must
conform with American National Standard--Z223.1--National Fuel
Gas Code, Latest Revision.
The available gas supply must agree with the required gas supply
marked on the unit nameplate. Minimum permissible gas supply
pressure for purpose of input adjustment must be at least 5.0" W.
C. (inches Water Column) for natural gas and 11' W.C. for propane.
PIPE DELIVERY SCHEDULE (NATURAL GAS ONLY)
NOTE: The following procedure and tables below apply to
Natural Gas only.
1.Obtain from the gas company the heating value and specific
gravity of the gas delivered.
2.Determine the exact length of pipe needed.
3.Read the BTUH input nameplate on the furnace.
4.Use the multiplier opposite the specific gravity of the gas given in
Table 1 below and insert in the following formula:
TABLE 1
MULTIPIERS TO BE USED
WHEN THE SPECIFIC
GRAVITY OF THE GAS IS
OTHER THAN 0.60
Furnace Input in BTUH
CFH =
Gas Heat Content in BTU/Cu. Ft. X Multiplier
This will give the factor for columns 2 through 6 in Table 2.
5.Using Table 2, select the pipe length nearest to yours.
6.Follow this line vertically down to the exact CFH found in Step 4
above or the next highest value.
7.Read horizontally to the left of this column for the required pipe
size diameter.
TABLE 2
NATURAL GAS ONLY
TABLE OF CUBIC FEET PER HOUR OF GAS
FOR VARIOUS PIPE SIZES AND LENGTHS
PIPE
LENGTH OF PIPE (feet)
SIZE
(inch)
10
20
1/2
132
92
3/4
278
190
152
1
520
350
285
1-1/4
1050
730
590
THIS TABLE IS BASED ON PRESSURE DROP OF 0.3 INCH W.C. AND 0.6 SP.GR. GAS

GAS PIPING INSTALLATION

SPECIFIC
MULTIPIER
GRAVITY
.50
.55
.60
.65
30
40
50
60
73
63
56
50
130
115
105
245
215
195
520
440
400
NOTE: If this is an propane application, consult your propane
supplier for pipe sizes and deliveries.
GAS PRESSURE SET-UP PRECAUTIONS
WARNING:
TO TEST FOR GAS LEAKS: AN EXPLOSION COULD
OCCUR, CAUSING INJURY OR DEATH.
IMPORTANT: The furnace and its individual shut-off valve
must be disconnected from the gas supply piping system
during any pressure testing of that system at test pressures
exceeding 1/2 psig (3.48 kPa).
The furnace must be isolated from the gas supply piping system by
closing its individual manual shut-off valve during any pressure
testing of the gas supply piping system at test pressures less than
or equal to 1/2 psig (3.48 kPa).
GAS SUPPLY LINE PRESSURE (ALL FUELS)
Before connecting the unit to the gas supply line, be sure to
determine the gas pressure in the line.
If the gas supply pressure is excessive (above 13.8 inches water
column or 1/2 psig), install a pressure regulator either at the supply
source or in the branch circuit serving the unit. Once the regulator
is installed, set it to provide a maximum pressure of 13.8" W.C. to
the gas valve for natural gas with a minimum supply pressure of 5.0"
W.C. Maximum supply pressure of 13.8" W.C. to the gas valve for
propane with a minimum pressure of 11.0" W.C.
1.10
NOTE: Maximum pressure to the gas valve for natural gas
1.04
is 13.8" W.C. Minimum pressure is 5.0" W.C. Maximum
pressure to the gas valve for propane is 13.8"W.C. Minimum
1.00
pressure to the gas valve is 11.0" W.C.
.962
If the supply line pressure is below the minimum supply pressure
indicated on the unit nameplate, contact the gas supply company.
Follow these steps to complete the installation of the unit gas piping.
See Figure 14.
1. Install a tapped, Style A (1/8-inch NPT tap) shut-off gas cock at
the end of the gas supply line near the unit. Be sure the tapped
gas cock is downstream of the pressure regulator, if used.
r
1/8" N.P.T.PLUGGED
ACCESS FOR TEST
GAUGE CONNECTION
FROM
GAS SUPPLY
70
46
FIELD SUPPLIED MAIN
96
GAS VALVE, MUST BE
180
INSTALLED BY DEALER
OUTSIDE UNIT.
370
NEVER USE AN OPEN FLAME
DEALER INSTALLED
GROUND UNION
6"
MIN
DRIP LEG
UNIT
TO MAIN
CONTROL
VALVE
Page 13