Trane X39641161-01B Installation And Configuration Manual page 2

Programmable

Advertisement

Installation Options (see configure on front side of page)
No.
Name
Default
Values/Descriptions
0100
Temperature
0
0
°F, 1 degree resolution
indication/
1
°F, 0.5 degree resolution
resolution
2
°C, 1 degree resolution
0110
Clock format
12
12 12 hour clock
0120
Year
09
09-99 2009-2099
0121
Month
1
1 - 12
0122
Day
1
1 - 31
0125
Daylight savings
2
0
Disabled
1
US (1987), changeover
at 2:00am
2
US (2007), changeover
at 2:00am
0126
Spring month
03
01-12
0127
Spring day
08
01-31
0128
Fall month
11
01-12
0129
Fall day
08
01-31
0130
System selection
8
1
1H/1C (conv) 1st Stage Heat (W), 1st Stage Comp (Y), Fan (G)
2
1H/1C (HP) 1st Stage Comp (Y), Changeover (O/B), Fan (G)
3
1H (Conv) 1st Stage Heat (W), without fan
4
1H (Conv) 1st Stage Heat (W), Fan (G)
5
1C (Conv) 1st Stage Comp (Y), Fan (G)
6
2H/1C (HP) 1st Stage Comp (Y), Changeover (O/B), Auxiliary Heat
(W1), Fan (G)
7
2H/2C (Conv) 1st & 2nd Stage Heat (W,W2), 1st & 2nd Stage
Comp (Y,Y2), Fan (G)
8
2H/1C (Conv) 1st & 2nd Stage Heat (W,W2), 1st Stage Comp (Y), Fan
(G)
9
1H/2C (Conv) 1st Stage Heat (W), 1st & 2nd Stage Comp (Y,Y2), Fan
(G)
10
2H/2C (HP) 1st & 2nd Stage Comp (Y,Y2), Changeover (O/B), Fan (G)
11 3H/2C (HP) 1st & 2nd Stage Comp (Y,Y2), Changeover (O/B),
Auxiliary Heat (W1), Fan (G)
0140
Schedule options
1
0
Non-programmable
0150
TOD/Economizer
0
0
Unused
output (terminal A)
1
TOD energizes terminal A during occupied period, not during
unoccupied period.
2
Economizer energizes terminal A during a call for cool.
0151
Heat fan operation
0
0
System controls fan
0153
Reversing value O/
0
0
O/B terminal energized in
B
cooling
0160
CPH 1st stage
3
1-5
compressor
0161
CPH 2nd stage
3
1-5
compressor
0162
CPH 1st stage
5
1-10
conventional heat
0163
CPH 2nd stage
9
1-10
conventional heat
0164
CPH for auxiliary
9
1-10
heat
0165
CPH for emergency
9
1-10
heat
0170
Continuous
0
0
Backlight turns off after 8
backlight
seconds.
0180
Changeover
1
0
Manual changeover
0181
Deadband
3
2
2° F (1° C)
3
3° F (1.5° C)
4
4° F (2.0° C)
5
5° F (2.5° C)
0182
Minimum comp off
5
0
Off (no minimum)
time (for systems
1
1 minute
with cool stage)
2
2 minutes
0190
Power supply
0
0
60Hz
frequency
Note: Some options are dependent on the system settings and may not appear during setup.
3
°C with 0.5 degree resolution
4
°C with 0.1 degree resolution
24 24 hour clock
3
Europe, changeover at
1:00am
4
Manual, changeover at
2:00am
Spring and fall daylight savings
months and days.
(These options are available if
option #0125 is set to 4).
1
Programmable
1
Thermostat controls fan
1
O/B terminal energized in
heating
Cycles per hour for 1st stage compressor. Only for
systems with cool or heat pump stage. Also changes
2nd stage cool default CPH.
Cycles per hour for 2nd stage compressor. Only for
systems with 2 cool or heat pump stages.
Cycles per hour for 1st stage conventional heat. Only for
systems with heat stages. Changes 2nd stage heat
default CPH.
Cycles per hour for 2nd stage conventional heat. Only for
systems with two conventional heat stages.
Cycles per hour for auxiliary heat. Only for heat pump
systems with more heat than cool stages.
Cycles per hour for emergency heat. Only for heat pump
systems with more heat than cool stages.
1
Backlight does not turn off
1
Automatic changeover
6
6° F (3.0° C)
7
7° F (3.5° C)
8
8° F (4.0° C)
9
9° F (4.5° C)
3
3 minutes
4
4 minutes
5
5 minutes
1
50Hz
No.
Name
Default
Values/Descriptions
0210
Temperature
0
0
Internal for H/C; display can showonly local temperature
sensor selection
and setpoint.
1
Internal for H/C, remote (connected to S1 & S2) for display; display
can show local and remote temperature, and setpoint.
2
Internal for H/C, remote (connected to S1 & S2) for compressor and
auxiliary lockout; display can show local and remote temperature,
and setpoint. (Disabled for conventional systems.)
3
Remote (connected to S1 & S2) for H/C, internal disabled; display
can show remote indoor temperature and setpoint.
0220
Heat pump
0
0
None
compressor
15 15° F (–9.5° C)
lockout point
20 20° F (–6.5° C)
25 25° F (–4.0° C)
Only available for heat pump systems with more heat than cool stages and
remote outdoor sensor. A 5 °F (2.5 °C) dead band between options #0220
and #0221 will be enforced automatically.
0221
Heat pump aux
0
0
None
lockout point
40 40° F (4.5° C)
45 45° F (7.0° C)
0230
Temp occupied
3
0
0 hours
duration limit
1
1 hour
For TOV override. When Setting 0 Hours, TOV Function Still Available.
0231
Number of periods
2
2
Two scheduling periods
per day
0232
Period occupied/
4
If option #0231 is set to 2
unoccupied
Day
definitions
0
UnOcc
1
UnOcc
2
UnOcc
3
UnOcc
4
Occ
5
Occ
6
Occ
7
Occ
8
UnOcc
9
UnOcc
10 UnOcc
11 UnOcc
12 Occ
13 Occ
14 Occ
15 Occ
0233
Scheduling mode
0
0
1 day. Mo-Su all days share the same schedule.
day options
1
5+1+1 days. Mo-Fr share a schedule. Sa and Su each have an
independent schedule.
2
5+2 days. Mo-Fr share a schedule. Sa-Su share a schedule.
3
7 days. Each day has an independent schedule.
0240
Heat temperature
90
40 - 90
range stops
4 - 32
0241
Cool temperature
50
50 - 99
range stops
10 - 37
0260
Temperature
0
–3 –3° F (–1.5° C)
display offset
–2 –2° F (–1.0° C)
–1 –1° F (–0.5° C)
0
None
Applies only to control temperature and display temperature for internal
and indoor remote sensor. Does not apply to outdoor temperature for
display.
0270
Extended fan-on
0
0
Off
time heat
90 90 seconds
0271
Extended fan-on
0
0
Off
time cool
40 40 seconds
0300
Restore factory
0
0
No - do not restore
defaults
1
Yes - reset all installer options to default except calendar, and system
selection. (Options 0120, 0121, 0122, 0130 do not reset.)
Trane optimize s the performance of home s and buildings a round the world. A business of Inger soll
Ra nd, the le ader in cre ating a nd susta ining safe, comfor table and e ne rgy efficient environments, Tra ne
offer s a br oa d portfolio of a dv anced contr ols a nd H VA C syste ms, compr ehensiv e building ser vices, and
par ts. For more infor ma tion, visit www.Trane.com.
© 2012 Trane. All rights reserved.
X39641161-01B 19 Mar 2012
Tra ne h as a pol ic y of c on tinu ous pro duc t an d prod uc t d ata im prove ment an d res erves the rig ht to c hang e
Supersedes X39641161-01A 03 Dec 2009
d es ig n an d sp ec ific ati ons wi thou t no tic e.
30 30° F (–1.0° C)
35 35° F (1.5° C)
40 40° F (4.5° C)
45 45° F (7.0° C)
50 50° F (10.0° C)
55 55° F (13.0° C)
60 60° F (15.5° C)
2
2 hours
3
3 hours
4
4 hours
4
Four scheduling periods
per day
If option #0231 is set to 4
Night
Morn, Day, Evening, Night
UnOcc
0
UnOcc, UnOcc, UnOcc, Unocc
Occ
1
UnOcc, UnOcc, Unocc, Occ
UnOcc
2
UnOcc, UnOcc, Occ, UnOcc
Occ
3
UnOcc, Unocc, Occ, Occ
UnOcc
4
UnOcc, Occ, UnOcc, UnOcc
Occ
5
UnOcc, Occ, UnOcc, Occ
UnOcc
6
UnOcc, Occ, Occ, UnOcc
Occ
7
UnOcc, Occ, Occ, Occ
UnOcc
8
Occ, UnOcc, UnOcc, UnOcc
Occ
9
Occ, UnOcc, UnOcc, Occ
UnOcc
10 Occ, UnOcc, Occ, UnOcc
Occ
11 Occ, UnOcc, Occ, Occ
UnOcc
12 Occ, Occ, UnOcc, UnOcc
Occ
13 Occ, Occ, UnOcc, Occ
UnOcc
14 Occ, Occ, Occ, UnOcc
Occ
15 Occ, Occ, Occ, Occ
40° F to 90° F
(Only applies to systems with
4° C to 32° C
heat stages)
40° F to 90° F
(Only applies to systems with cool
4° C to 32° C
stages)
1
1° F (0.5° C)
2
2° F (1.0° C)
3
3° F (1.5° C)
(Only available when option #0151
is set to 1)
(Only available on systems with
cool stages, see option #0130)