AIR FOR COMBUSTION AND VENTILATION
Ventilation Air From Outdoors
Provide extra fresh air by using ventilation
grills or ducts. You must provide two perma-
nent openings: one within 12" of the ceiling
and one within 12" of the floor. Connect these
items directly to the outdoors or spaces open
to the outdoors. These spaces include attics
and crawl spaces. Follow the National Fuel
Gas Code ANSI Z223.1/NFPA 54, Air for
Combustion and Ventilation for required size
of ventilation grills or ducts.
IMPORTANT: Do not provide openings for
inlet or outlet air into attic if attic has a thermo-
stat-controlled power vent. Heated air entering
the attic will activate the power vent.
Outlet
Air
Outlet
Air
Inlet
Air
Inlet Air
Figure 3 - Ventilation Air from Outdoors

INSTALLATION

NOTICE: This heater is intended
for use as supplemental heat.
Use this heater along with your
primary heating system. Do not
install this heater as your pri-
mary heat source. If you have a
central heating system, you may
run system's circulating blower
while using heater. This will help
circulate the heat throughout the
house. In the event of a power
outage, you can use this heater
as your primary heat source.
WARNING: A qualified ser-
vice person must install heater.
Follow all local codes.
8
Continued
Ventilated
Attic
To Attic
To
Crawl
Space
Ventilated
Crawl Space
www.SuperiorFireplaces.US.com
NOTICE: State or local codes may
only allow operation of this appliance
in a vented configuration. Check your
state or local codes.
WARNING: Before installing in
a solid fuel burning fireplace, the
chimney flue and firebox must be
cleaned of soot, creosote, ashes and
loose paint by a qualified chimney
cleaner. Creosote will ignite if highly
heated. A dirty chimney flue may
create and distribute soot within
the house. Inspect chimney flue
and firebox for damage. If damaged,
repair flue before operating heater.
WARNING: Any outside air ducts
and/or ash dumps in the fireplace
shall be permanently closed at time
of appliance installation.
WARNING: Seal any fresh air
vents or ash clean-out doors located
on floor or wall of fireplace. If not,
drafting may cause pilot outage
or sooting. Use a heat-resistant
sealant. Do not seal chimney flue
damper.
WARNING: Never install the
heater
• in a bedroom or bathroom
• in a recreational vehicle
• where curtains, furniture, cloth-
ing or other flammable objects
are less than 36" from front or
42" from top of heater. For side
clearances see Figure 4, page 9
• in high traffic areas
• in windy or drafty areas
126838-01A