Superior VD1824PM Installation And Operation Instructions Manual page 14

Unvented gas log heater
Table of Contents

Advertisement

WARNING: Never connect
natural gas fireplace to private
(non-utility) gas wells. This gas
is commonly known as wellhead
gas.
CAUTION: Use only new,
black iron or steel pipe. Inter-
nally-tinned copper tubing may
be used in certain areas. Check
your local codes. Use pipe of
1/2" diameter or greater to allow
proper gas volume to heater. If
pipe is too small, undue loss of
volume will occur.
Installation must include an equipment shutoff
valve, union and plugged 1/8" NPT tap. Locate
NPT tap within reach for test gauge hook up.
NPT tap must be upstream from heater (see
Figure 14).
IMPORTANT: Install equipment shutoff valve
in an accessible location. The equipment
shutoff valve is for turning on or shutting off
the gas to the appliance.
Check your building codes for any special
requirements for locating equipment shutoff
valve to fireplaces.
Apply pipe joint sealant lightly to male NPT
threads. This will prevent excess sealant from
going into pipe. Excess sealant in pipe could
result in clogged heater valves.
WARNING: Use pipe joint
sealant that is resistant to liquid
petroleum (LP) gas.
We recommend that you install a sediment trap
in supply line as shown in Figure 14. Locate
sediment trap where it is within reach for
cleaning. Install in piping system between
fuel supply and heater. Locate sediment trap
where trapped matter is not likely to freeze.
A sediment trap traps moisture and contami-
nants. This keeps them from going into heater
controls. If sediment trap is not installed or is
installed wrong, heater may not run properly.
14
INSTALLATION
Continued
www.SuperiorFireplaces.US.com
Equipment Shutoff
Valve With 1/8"
NPT Tap*
Approved
Flexible
Gas Hose (if
allowed by
local codes)
3" Minimum
Gas
Control
Figure 14 - Gas Connection
* Purchase the optional equipment shutoff
valve from your dealer.
** Minimum inlet pressure for purpose of input
adjustment.
CAUTION: Avoid damage to
gas control. Hold gas fitting with
wrench when connecting it to
gas piping and/or fittings.
CHECKING GAS CONNECTIONS
WARNING: Test all gas piping
and connections, internal and
external to unit, for leaks after
installing or servicing. Correct
all leaks at once.
WARNING: Never use an
open flame to check for a leak.
Apply a noncorrosive leak detec-
tion fluid to all joints. Bubbles
forming show a leak. Correct all
leaks at once.
PROPANE/LP
From External
Regulator (11"
W.C.** to 14" W.C.
Pressure)
NATURAL
From Gas Meter
(5" W.C.** to
10.5" W.C.
Pressure)
Cap
Pipe Tee
Nipple Joint
Sediment Trap
126838-01A

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Vd1824nm

Table of Contents