Refrigerant recovery method

※ Please perform the refrigerant recovery
according to the local law and rules.
The refrigerant recovery of this type
of equipment must be performed by a
refrigerant recovery machine.
Turn on both the power supplies of the
outdoor unit and the branch boxes.
Press the "MODE/EXIT" button of the
outdoor unit when all units are in stop
operation state.
Match the 7 seg. display to "F3" by
pushing the SELECT button.
Press the "ENTER" button.
Match the 7 seg. display to "21" by
pushing the "SELECT" button.
Press the "ENTER" button for about 5
seconds.
Turn off the power supplies of all units
when "P.oFF" is displayed.
Perform the refrigerant recovery with
the refrigerant recovery machine.
It can not be operated in the "P.oFF" state.
Please turn on the power supplies of all units again in case of performing operation.