SYSTEM CONFIGURATION

41 11

Piping limitation and Pipe size

Outdoor
Unit
Outdoor
Unit
H2
H2
H1
H1
Pipe limitation
Maximum total equivalent pipe length
Maximum total equivalent pipe length
Between outdoor unit and the farthest indoor unit
Between outdoor unit and the farthest indoor unit
Between outdoor unit and branch boxes
Between outdoor unit and branch boxes
Between branch box and indoor unit
Between branch box and indoor unit
Between outdoor unit and the first separation tube
Between outdoor unit and the first separation tube
Between outdoor unit and branch box (when there is no separation tube
Between outdoor unit and branch box (when there is no separation tube
Between outdoor unit and indoor unit
Between outdoor unit and indoor unit
Between outdoor unit and branch box
Between outdoor unit and branch box
Between branch box and branch box
Between branch box and branch box
Between indoor unit and indoor unit
Between indoor unit and indoor unit
Pipe size selection
Between outdoor unit and first
separation tube
Between first separation tube and
second separation tube
Between separation tube and
branch box
Between branch box and indoor unit
CAUTION
Separation Tube
Separation Tube
b
a
b
a
d
d
H3
(Primary)
H3
(Primary)
Branch Box
Branch Box
g
f
g
f
h
h
Indoor
Indoor
Unit2
Indoor
Unit1
Indoor
Unit2
Unit1
Indoor
Unit3
Indoor
Unit3
Diagram
a
b
c, d, e
f, g, h, i,
j, k, l, m
e
(Secondary1)
e
(Secondary1)
Branch Box
Branch Box
i
j
i
k
j
k
Indoor
Unit4
Indoor
Unit4
Indoor
Indoor
H4
Unit5
Unit6
Indoor
Indoor
H4
Unit5
Unit6
Limitation
Limitation
m (ft)
m (ft)
115 or less (377)
115 or less (377)
70 or less (230)
70 or less (230)
55 or less (180)
55 or less (180)
Total
60 or less (197)
Total
60 or less (197)
Each unit
Between 3-15 (10-49)
Each unit
Between 3-15 (10-49)
5 or more (16)
5 or more (16)
5 or more (16)
5 or more (16)
30 or less (98)
30 or less (98)
30 or less (98)
30 or less (98)
15 or less (49)
15 or less (49)
15 or less (49)
15 or less (49)
Condition
(Model code of indoor unit)
7 ,9, 12
18
24
c
c
(Secondary2)
(Secondary2)
Branch Box
Branch Box
l
l
m
m
Indoor
Unit7
Indoor
Unit7
Indoor
Unit8
Indoor
Unit8
Diagram
Diagram
Total
Total
a + b + c + m
a + b + c + m
a + b + c + d + e
a + b + c + d + e
f + g + h + i + j + k + l + m
f + g + h + i + j + k + l + m
f, g, h, i, j, k, l, m
f, g, h, i, j, k, l, m
a
a
a+d
a+d
H1
H1
H2
H2
H3
H3
H4
H4
Gas pipe
Liquid pipe
(mm(in.))
(mm(in.))
Φ15.88 (5/8)
Φ9.52 (3/8)
Φ15.88 (5/8)
Φ9.52 (3/8)
Φ15.88 (5/8)
Φ9.52 (3/8)
Φ9.52 (3/8)
Φ6.35 (1/4)
Φ12.70 (1/2)
Φ 6.35 (1/4)
Φ15.88 (5/8)
Φ6.35 (1/4)
En-11