External Static Pressure - Toshiba MMD-AP0076BH-E Installation Manual

Table of Contents

Advertisement

2
Each time
button is pushed, indoor
unit numbers in the control group change
cyclically. Select the indoor unit to change
settings for.
The fan of the selected unit runs and the louvers
start swinging. The indoor unit for change settings
can be confirmed.
3
Specify CODE No. [
] with "TEMP."
buttons.
4
Select SET DATA [
] with "TIME"
buttons.
5
Push
button. When the display changes
from flashing to lit, the setup is completed.
• To change settings of another indoor unit,
2
repeat from Procedure
.
• To change other settings of the selected indoor
3
unit, repeat from Procedure
.
• Use
button to clear the settings. To make
settings after
button was pushed, repeat
2
from Procedure
.
6
When settings have been completed, push
button to determine the settings.
When
button is pushed,
and then the display content disappears and
the air conditioner enters the normal stop
mode.
(While
is flashing, no operation of the
remote controller is accepted.)
31-EN
 External static pressure
settings
<Change on wired remote controller>
Set up a tap change based upon the external static
pressure of the duct to be connected.
To set up a tap change, follow to the basic operation
1
2
3
4
5
procedure (
• Specify [5d] to the CODE No. in procedure
• For the SET DATA of procedure
DATA of the external static pressure to be set up
from the following table.
/
SET DATA

External static pressure

0000
40 Pa
(Factory default)
/
0001
30 Pa
(Factory default)
0002
65 Pa
0003
50 Pa
(Factory default)
0004
80 Pa
0005
100 Pa
0006
120 Pa
The list above is when SW501-1 and SW501-2 is OFF.
If the setting is wrong, "P12" may appear indicating a
fan motor error.
flashes
<Setting up on the circuit board of the indoor unit>
To set up the external static pressure, use the DIP switch on the circuit board of the wireless reception part.
For details, refer to the instruction manual of the wireless remote controller kit. Alternatively, use the switch on the
indoor micro computer circuit board as shown in the following figure and table.
6
).
3
.
4
, select a SET
AP024 to 030
AP007 to 018
AP036 to 058
– 16 –
SW501
SW501-1
SW501-2
SET DATA
To reset to the factory default
Switch off SW501-1 and SW501-2, connect a separately-sold
wired remote controller, and then perform the procedure for
installing a separately-sold filter on this page to set the [5d] data
to "0000".
OFF
ON
OFF
ON
OFF
OFF
ON
ON
Factory
0001
0003
0006
default
32-EN