5.
CAPACITY COMPENSATION RATE FOR PIPE LENGTH
AND HEIGHT DIFFERENCE
This table is created using the maximum capacity.
MODEL
: AOG12LALL
COOLING
Indoor unit is
higher than
outdoor unit.
Height
difference H
(m)
Indoor unit is
lower than
outdoor unit.
HEATING
Indoor unit is
higher than
outdoor unit.
Height
difference H
(m)
Indoor unit is
lower than
outdoor unit.
Indoor unit
Connection pipe
1 Indoor unit is higher than outdoor unit.
5
15
-
Û 1
10
-
7.5
-
5
0.992
0
1.000
-5
1.000
Û 2
-7.5
-
-10
-
-15
-
5
15
-
Û 1
10
-
7.5
-
5
1.000
0
1.000
-5
0.995
Û 2
-7.5
-
-10
-
-15
-
Height difference H
H
Outdoor unit
- (02 - 06) -
Pipe length (m)
7.5
10
15
-
-
0.903
-
0.964
0.918
0.988
0.968
0.922
0.992
0.972
0.925
1.000
0.980
0.933
1.000
0.980
0.933
1.000
0.980
0.933
-
0.980
0.933
-
-
0.933
Pipe length (m)
7.5
10
15
-
-
0.943
-
1.010
0.943
1.000
1.010
0.943
1.000
1.010
0.943
1.000
1.010
0.943
0.995
1.005
0.939
0.993
1.002
0.936
-
0.999
0.934
-
-
0.925
Outdoor unit
H
Indoor unit
Connection pipe
2 Indoor unit is lower than outdoor unit.
20
25
0.894
0.867
0.909
0.881
0.912
0.885
0.916
0.888
0.923
0.895
0.923
0.895
0.923
0.895
0.923
0.895
0.923
0.895
20
25
0.916
0.896
0.916
0.896
0.916
0.896
0.916
0.896
0.916
0.896
0.912
0.892
0.909
0.890
0.907
0.887
0.898
0.878