Operation Details
Heating Mode Operation
The unit will operate according to the setting by the remote controller and the operation diagram is shown as following.
Intake Air Temperature
Setting Temperature +3°C
(Compressor OFF)
Setting Temperature
(Compressor ON)
INDOOR FAN
COMPRESSOR
• A point;
While the indoor Heat-Exchanger temperature is higher than 40°C fan operates at low speed,
when it becomes lower than 40˚C fan stops.
• B point;
When the indoor Heat-Exchanger temperature is higher than 42°C, fan operates at seleted fan
speed, when it becomes lower than 39°C, the fan operates at low speed.
Hot-Start Control
• The indoor fan does not rotate until the evaporator piping temperature reaches 25°C.
• The operation diagram is as following.
68
Indoor Unit
minimum 3min
1min
Selecting
Hot Start
Low
Fan Speed
ON
PIPING
TEMPERATURE
25°C
22°C
INDOOR FAN
COMPRESSOR
: Selected Fan
A
minimum
10sec.
Low
OFF
Low
OFF
1min
ON
: Low Fan
: Fan Stop
B
minimum
10sec.
Selecting fan
Low
speed
ON
A
OFF
OFF