Facing
1. Combustible wall (such as drywall panels) must be installed flush with the fireplace. It may not project in front of and on the fireplace (i.e. the
steel facade of the fireplace (see Figure 13).
2. Decorative frame made of combustible material cannot project in front of and on the fireplace steel front, in the space delimited by the width of
the unit (38") and a height of 54" from the base of the appliance (see Figure 15).
3. Non-combustible materials such as brick, stone or ceramic tile may project in front of and onto the fireplace facing (see Figure 14).
Mantel
The mantel must be installed at least 54" (1372 mm) above the base of the fireplace (see Figure 13).
*NOTE: Mantel can be reduced to 48" (1219 mm) if the Clean Face Panel option is installed with the gravity kit.
*
54"
Figure 13
12
1/2" GYPSUMBOARD
2" x 3" MIN.
SPACER
MANTEL
54"
Figure 15
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
NON
COMBUSTIBLE
FACING
Figure 14
38"
COMBUSTIBLE
CAN NOT
PROJECT OVER
OR IN FRONT
OF THE
FIREPLACE
1/2" GYPSUMBOARD
2" x 3" MIN.
SPACER