General - Viessmann VITODENS 200-W Service Instructions Manual

Wall-mounted, gas-fired condensing boiler natural gas and lpg version
Table of Contents

Advertisement

Coding 2

General

Calling up coding level 2
Note: At coding level 2, all codes are accessible,
including the codes at coding level 1.
Codes that have not been assigned due to the
heating system equipment level or the setting of
other codes are not displayed.
Heating systems with one heating circuit without
mixing valve and one or two heating circuits with
mixing valve:
The heating circuit without mixing valve is
designated "Heating circuit 1" and the heating
circuits with mixing valve as "Heating circuit 2"
or "Heating circuit 3".
Select "General"
Coding
Coding in the factory setting
00:1
Value address
System type
00: ...
2
1
3
2
4
2
5
3
6
3
48
System type 1:
One heating circuit without
mixing valve A1 (heating circuit
1), without DHW heating
Description
One heating circuit without mixing valve A1 (heating circuit 1), with DHW
heating (code is adjusted automatically).
One heating circuit with mixing valve M2 (heating circuit 2), without DHW
heating.
One heating circuit with mixing valve (heating circuit 2), with DHW heating.
One heating circuit without mixing valve A1 (heating circuit 1) and
one heating circuit with mixing valve M2 (heating circuit 2), without DHW
heating (code is adjusted automatically).
One heating circuit without mixing valve A1 (heating circuit 1) and
one heating circuit with mixing valve M2 (heating circuit 2), with DHW
heating (code is adjusted automatically).
Vitodens 200-W B2HA 112, 150 Service
If the heating circuits were given individual designations,
the selected designation and "HC1", "HC2" or "HC3"
appear instead:
1. Press OK and
simultaneously for approximately
4 seconds.
2. Press OK and
simultaneously for approximately
4 seconds.
3. "Coding level 2"
4. Select group of required coding address:
- "General"
- "Boiler"
- "DHW"
- "Solar"
- "Heating circuit 1/2/3"
- "All cod. or solar"
In this group, all coding addresses (except the
coding addresses from the "Solar" group) are
displayed in ascending order.
5. Select coding address.
6. Select value according to the following tables and
confirm with "OK".
7. If you want to reset all codes to their factory setting:
Select "Standard setting" in "Coding level 2".
Note: This also resets codes at coding level 1.
Possible change
00:2
For system type, see the
to
following table:
00:10