Set Maximum Input; Check All Primary And Secondary Circuit Connections For Leaks; Perform Combustion Analysis - Viessmann VITODENS 200-W Service Instructions Manual

Wall-mounted, gas-fired condensing boiler natural gas and lpg version
Table of Contents

Advertisement

Start-up and Service

Set Maximum Input

Check All Primary and Secondary Circuit Connections for Leaks

Perform Combustion Analysis

20
Vitodens 200-W B2HA 112, 150 Service
The maximum input (or output) for heating operation can
be limited. The limit is set via the modulation range. The
maximum adjustable heating input (or output) is limited
upwards by the boiler coding card.
Note: The input for DHW production can be limited as
well. To do so, change coding address "6F" in
coding level 2.
1. Press OK and
simultaneously for approximately
4 seconds.
2. "Service functions"
3. "Maximum output"
4. "Change?" Select "Yes".
A value flashes on the display (e.g."85"). In the
factory setting, this value represents 100%
of rated input (or output).
5. Select required value.
Check heating system and domestic hot water
connections (if applicable). Ensure all connections
are pressure tight. Correct any leaks found on fittings,
pumps, valves, etc.
IMPORTANT
A CO measurement (see page 28) must be taken before
and after working on gas appliances to eliminate risks to
health and to guarantee the satisfactory condition of the
system.
Record the measured combustion values in the sequence
stated in the Maintenance Record on page 100 in this
manual.

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Vitodens 200-w b2ha 112Vitodens 200-w b2ha 150

Table of Contents