Outdoor Unit (Ras-18Ua-Es2) - Toshiba RAS-24UKHP-ES-1 Service Manual

Toshiba split wall type air conditioner service manual
Table of Contents

Advertisement

10-4 Outdoor Unit (RAS-18UA-ES2)

No.
Part name
1
Common
procedure
2
Running
capacitor
for compressor
3
Running
capacitor
for fan motor
4
Relay
5
Spark killer
6
Bimetal thermostat
Procedures
1) Stop the operation of the air conditioner and turn off
its main power supply or remove the power supply
cord.
2) Remove the electrical parts cover.
(2 screws ∅4 x 10L)
3) Remove 2 cord clamps (4 screws ∅4 x 22L) and
disconnect the power supply cord and connecting
cable after removing 6 screws on the terminal block
and 1 ground screw on the electrical parts base.
4) Remove the front cabinet. (8 scerws ∅4 x 10L)
(Pull the front lower portion toward you, and pull out
it upward to remove it.)
5) Remove the back cabinet. (4 screws ∅4 x 10L)
1) Perform the common procedure 1
2) Remove the capacitor band. (1 screw ∅4 x 10L)
3) Disconnect the lead wires from the capacitor
terminal.
1) Perform the common procedure 1
2) Remove the fixing screw. (1 screw ∅4 x 10L)
3) Disconnect the lead wires from the capacitor
terminal.
1) Perform the common procedure 1
2) Unlatch the relay and pull it upward.
3) Disconnect the lead wires from the relay terminal.
1) Perform the common procedure 1
2) Remove the fixing screw. (1 screw ∅4 x 10L)
3) Disconnect the lead wires from the terminal.
1) Perform the common procedure 1
2) Remove the terminal cover of compressor.
3) Remove the thermostat holder from the
compressor.
4) Disconnect the lead wires from the bimetal
thermostat.
Remove
8 screws ∅4 x 10L
4 screws ∅4 x 22L
Running
capacitor for
compressor
Running
capacitor for
fan motor
Spark killer
– 67 –
FILE NO. SVM-03009
Remarks
4 screws ∅4 x 10L
Relay
Bimetal thermostat

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents