MLCAC-UTSM-2010-10 Contents Part 1 General Information ....................1 Part 2 Indoor Units ......................7 Part 3 Outdoor Units ......................86 Part 4 Installation ......................124 Part 5 Control........................135 ※The specifications, designs, and information in this book are subject to change without notice for product improvement.
MLCAC-UTSM-2010-10 General Information Part 1 General Information 1. Model Names of Indoor/Outdoor Units ......2 2. External Appearance ............3 2.1 Indoor Units ................. 3 2.2 Outdoor Units ................4 3. Nomenclature ..............5 4. Features ................6 General Information...
Cooling and heating 1.2 Outdoor Units Model of outdoor unit and corresponding indoor unit Universal Outdoor unit Model Compressor type Compressor Brand Matched indoor units KCA2-12HRDN1-Q KTB-12HWDN1 KOU-12HDN1 Rotary DC Inverter GMCC KUB-12HRDN1 KFA-12HRDN1 KCA2-18HRDN1-Q KTB-18HWDN1 KOUA-18HDN1-C0 Scroll DC Inverter...
MLCAC-UTSM-2010-10 Nomenclature 3. Nomenclature 3.1 Indoor Unit M U B - 18 H R D N1 Refrigerant Type N1 R410A DC Inverter Control Mode R Remote Control Function Code C cooling Only H cooling & Heating Capacity (¡ Á 1 000Btu/h) Product Series A First Time Design B Second Time Design C Third Time Design...
Features MLCAC-UTSM-2010-10 4. Features 4.1 Universal outdoor unit design Indoor unit with the same capacity can match with the same outdoor unit. 4.2 High efficiency and energy saving. Thanks to the DC inverter technology and optimized piping system, the EER and COP of whole series can easily reach A-class.
Page 11
MLCAC-UTSM-2010-10 Indoor Units Part 2 Indoor Units New Four-way Cassette Type (Compact) ......8 Four-way Cassette Type ............ 18 Duct Type ................35 Ceiling & Floor Type ............53 Console Type ..............72 Indoor Units...
Page 12
New Four-way Cassette Type (Compact) MLCAC-UTSM-2010-10 New Four-way Cassette Type (Compact) 1. Features ................9 2. Specifications ..............10 3. Dimensions ..............11 4. Service Space ..............11 5. Wiring Diagrams ............12 6. Air Velocity and Temperature Distributions ....13 7.
MLCAC-UTSM-2010-10 Features 1. Features (1) Low operation noise ---Streamline plate ensures quietness ---Creates natural and comfortable environment (2) Efficient cooling ---Equal, fast and wide—range cooling (3) The adoption of the most advanced 3- Dimensional Screw fan ---Reduces the air resistance passing through ---Smoothes the air flow ---Makes air speed distribution to the heat exchange uniform (4) Improvement for easy installation and maintenance...
MLCAC-UTSM-2010-10 Air Velocity and Temperature Distributions 6. Air Velocity and Temperature Distributions Airflow velocity Temperature New Four-way Cassette (Compact)
Electric Characteristics MLCAC-UTSM-2010-10 7. Electric Characteristics Power Indoor Units Supply Model Min. Max. KCA2-12HRDN1-Q 220-240V 198V 254V KCA2-18HRDN1-Q 220-240V 198V 254V Remark: MFA: Max. Fuse Amps. (A) 8. Sound Levels FOUR-WAY CASSETTE TYPE 1.0m Microphone Noise level dB(A) Model KCA2-12HRDN1-Q KCA2-18HRDN1-Q New Four-way Cassette (Compact)
Four-way Cassette Type MLCAC-UTSM-2010-10 Four-way Cassette Type 1. Features ................19 2. Specifications ..............22 3. Dimensions ..............25 4. Service Space ..............26 5. Wiring Diagrams ............27 6. Air Velocity and Temperature Distributions ....28 7. Electric Characteristics ..........29 8.
MLCAC-UTSM-2010-10 Features 1. Features (1) Low operation noise —Streamline plate ensures quietness —Creates natural and comfortable environment (2) Efficient cooling——Equal, fast and wide range cooling (3) Excellent performance. The optimal evaporator & sufficient airflow volume guarantees the excellent capacity (4) The adoption of the most advanced 3- Dimensional Screw fan —Reduces the air resistance passing through —Smoothes the air flow —Makes air speed distribution to the heat exchange uniform...
Page 24
Features MLCAC-UTSM-2010-10 (8) Different color panels for choose: White、Gray、Blue、Black (9) Swing angle of louver Add one more swing motor, one motor driving two louvers. Controlling the interspace of each part, minimizing the angle loss. The swing angle of the first louver are 40~42 degrees and the second louver are 37~38 degrees. New evaporator and inner configuration designed can acquire high heat-exchanger effect.
Page 25
MLCAC-UTSM-2010-10 Features (15) Reserve spaces for air side-outlet, it is available to connect duct pipe hence air supplying from the four sides to nearby small room.. (16) The connecting pipe and drop height is higher. Max. pipe length up to 50m (refer to ①) , and Max. drop height up to 30m(refer to ②).
Features MLCAC-UTSM-2010-10 1. Features ● New structure design. ● Built-in drainage pump (Optical). ● Two air intake ways: from below or rear (standard). ● Wire controller is standard. ● Three speeds indoor unit. ● Fresh air inlet hole is reserved. Duct Type...
MLCAC-UTSM-2010-10 Service Space 4. Service Space Ensure enough space required for installation and maintenance. All the indoor units reserve the hole to joint the fresh air pipe. The hole size as following: Duct Type...
Wiring Diagrams MLCAC-UTSM-2010-10 5. Wiring Diagrams KTB-12HWDN1 KTB-18HWDN1 KTB1-24HWDN1 KTB-30HWDN1 KTB-36HWDN1 KTB-48HWDN1 KTB-60HWDN1 TO WIRE DISPLAY BOARD 202 07 03903 85 CONTROLLER C ODE T ITLE FAN MOTO R PU MP M OTOR CN1 0 CN 11 WAT ER L EVEL SWI TCH H /P2 HIG H FA N CH /P3...
MLCAC-UTSM-2010-10 Static Pressure 6. Static Pressure KTB-12HWDN1 KTB-18HWDN1 Super high speed High speed Super high speed Mid speed High speed Mid speed Low speed Low speed 200 300 400 500 1000 1100 1200 Air volume(m /h) Air volume(m /h) KTB1-24HWDN1 KTB-30HWDN1 Super high speed High speed...
Page 48
Static Pressure MLCAC-UTSM-2010-10 KTB-36HWDN1 KTB-48HWDN1 Super high speed Super high speed High speed High speed Mid speed Mid speed Low speed Low speed 1800 2000 1100 1200 1400 1600 2200 2400 Air volume(m /h) 1000 1300 1600 1900 2200 2500 2800 3100 Air volume(m /h)
MLCAC-UTSM-2010-10 Ceiling & Floor Type Ceiling & Floor Type 1. Features ................54 2. Specifications ..............55 3. Dimensions ..............58 4. Service Space ..............60 5. Wiring Diagrams ............61 6. Air Velocity and Temperature Distributions ....63 7. Electric Characteristics ..........65 8.
Features MLCAC-UTSM-2010-10 1. Features 1.1. New design, more modern and elegant appearance. 1.2. Convenient installation --The ceiling type can be easily installed into a corner of the ceiling even if the ceiling is very narrow --It is especially useful when installation of an air conditioner in the center of the ceiling is impossible due to a structure such as one lighting.
Console Type MLCAC-UTSM-2010-10 Console Type 1. Features ................73 2. Specifications ..............74 3. Dimensions ..............75 4. Service Space ..............76 5. Wiring Diagrams ............77 6. Air Velocity and Temperature Distributions ....78 7. Electric Characteristics ..........79 8.
MLCAC-UTSM-2010-10 Features 1. Features 1.1. Consumes up to 30% less energy than non-inverter units ——DC inverter compressor ——indoor fan motor adopts DC motor 1.2. Achieves set temperature more quickly ——air supplying from top and bottom or from top only ——air inlet from four directions 1.3.
MLCAC-UTSM-2010-10 Wiring Diagrams 5. Wiring Diagrams KFA-12HRDN1 KFA-18HRDN1 FUNCTION OF SWITCHES TO WIRE CONTROLLER SWITCH BOARD SWITCH BOARD DIS PLAY BOARD WIRING DIAGRAM INDOOR UNIT CN10 CN1 5 CODE PART NAME TEMP.COMPEN S A TIO N C N1-20 P.C BOARD SOCKETS TEM P.
Air Velocity and Temperature Distributions MLCAC-UTSM-2010-10 6. Air Velocity and Temperature Distributions Discharge angle 60 Airflow velocity Temperature Console Type...
MLCAC-UTSM-2010-10 Electric Characteristics 7. Electric Characteristics Indoor Unit Power Supply Model Voltage KFA-12HRDN1 220~240V 198V 254V KFA-18HRDN1 220~240V 198V 254V Remark: MFA: Max. Fuse Amps. (A) Console Type...
MLCAC-UTSM-2010-10 Specification 1. Specification Model KOU-12HDN1 KOUA-18HDN1-C0 name Outdoor Code 220075100071 220075200340 Power 220~240V-1 Ph-50Hz 220~240V-1 Ph-50Hz supply Max. input consumption 1500 2400 Max. current 13.1 Model C-6RVN93H0V DA108X1C-20FZ3 Type Rotary DC Inverter Scroll DC Inverter Brand Shenyang SANYO GMCC...
Page 92
Specification MLCAC-UTSM-2010-10 Model KOUB-24HDN1 KOU-30HDN1 name Outdoor Code 220075301070 220075401041 Power 220~240V-1 Ph-50Hz 220~240V-1 Ph-50Hz supply Max. input consumption 3250 4600 Max. current 15.48 Model ATL165SD-C9AU TNB220FLBM1 Type Rotary DC Inverter Rotary DC Inverter Brand HITACHI MITSUBISHI ELECTRIC Compressor Capacity Btu/h 15525 24328...
Page 93
MLCAC-UTSM-2010-10 Specification Model KOU-36HDN1 KOUB-36HDN1-R name Outdoor Code 220075500651 220075500920 Power 220~240V-1 Ph-50Hz 380V~3 Ph-50Hz supply Max. input consumption 5500 5500 Max. current Model TNB306FPGM TNB306FPNM Type Rotary DC Inverter Rotary DC Inverter Brand MITSUBISHI ELECTRIC MITSUBISHI ELECTRIC Compressor Capacity Btu/h 33642 33710...
Page 94
Specification MLCAC-UTSM-2010-10 Model KOU-48HDN1 KOUB-48HDN1-R name Outdoor Code 220075700341 220075700690 Power 220~240V-1 Ph-50Hz 380V~3 Ph-50Hz supply Max. input consumption 6000 6000 Max. current Model TNB306FPGM TNB306FPNM Type Rotary DC Inverter Rotary DC Inverter Brand MITSUBISHI ELECTRIC MITSUBISHI ELECTRIC Compressor Capacity Btu/h 33642 33710...
Page 95
MLCAC-UTSM-2010-10 Specification Model KOUA-60HRDN1 KOUD-60HDN1-R name Outdoor Code 220075800161 220075801220 Power 380V~-3 Ph-50Hz 380~415V-3 Ph-50Hz supply Max. input consumption 7500 7200 Max. current Model ANB42FBEMT ANB42FBEMT Type Scroll DC Inverter Scroll DC Inverter Brand MITSUBISHI MITSUBISHI Compressor Capacity Btu/h 47440 47440 Input 4160...
Page 111
MLCAC-UTSM-2010-10 Troubleshooting 1. Operation lamp flashes Operation lamp flashes at 5Hz Judge 1: Indoor temp. sensor is abnormal Check whether the resistance of the evaporator temp. sensor is Replace evaporator temp. sensor correct according to Annex 1 Judge 2: Room temp. sensor is abnormal Check whether the resistance of the room temp.
Page 112
Troubleshooting MLCAC-UTSM-2010-10 2. Timer lamp flashes Timer lamp flashes at 5Hz Judge: Indoor/outdoor unit communication is abnormal Refer to the outdoor unit LED display E2 malfunction in the following part 3. Alarm lamp slow-flash Indoor alarm lamps flash at 1Hz Condenser temp.
Page 113
MLCAC-UTSM-2010-10 Troubleshooting 4. Alarm lamp quick-flash Alarm lamp flashes at 5Hz Judge: Water level switch is abnormal. Replace water pump Check whether the water pump can work normally Select the cooling mode to make water pump work for a few minutes, then check Trouble is solved whether the system can run normally Solve to make the water can flow...
Page 114
Troubleshooting MLCAC-UTSM-2010-10 9.2 Outdoor unit malfunction Display Malfunction or Protection EEPROM malfunction Communication malfunction between indoor IC and outdoor IC Communication malfunction in outdoor IC and DSP Malfunction of outdoor temperature sensor Voltage protection of compressor PFC module protection (Only for 30K, 36K & 48K with 1 phase) Top temperature protection of compressor High pressure protection Low pressure protection...
Page 115
MLCAC-UTSM-2010-10 Troubleshooting 2. E2 malfunction E2 display Communication malfunction between indoor IC and outdoor IC Judge 1: Check whether the indoor unit power is on Turn on the indoor unit power Judge 2: Check whether the signal wiring is shield cable or whether Adopt the shield cable/ let shield cable earthed the shield cable is earthed Judge 3: Check whether the signal wiring between the indoor and...
Page 116
Troubleshooting MLCAC-UTSM-2010-10 3. E3 malfunction (For 18K & 24K & 30K) E3 display Communication malfunction in outdoor IC and DSP Check whether the indicator lights LED1 on the main board is flashing Replace the outdoor main board Insert the connecting wiring well over Check whether the connecting wiring between the IPM module and the CN4 again on the main board is broken off...
Page 117
MLCAC-UTSM-2010-10 Troubleshooting 4. E3 malfunction (For 36K & 48K & 60K) E3 display Communication malfunction in outdoor IC and DSP Check whether the indicator lights LED1 or LED2 on the main control board are flashing Replace PCB Install the IC-U3 chip of the PCB over again, check whether the system Trouble is solved can run normally Check whether the output of the transformer to CN4 socket is well...
Page 118
Troubleshooting MLCAC-UTSM-2010-10 5. E4 malfunction E4 display Judge 1: Outdoor condenser temp. sensor (T3) is malfunction Connect the wiring well Check whether the wiring of the condenser temp. sensor is broken off Check whether the resistance of condenser temp. sensor is wrong refer to the Annex 1 Replace condenser temp.
Page 119
MLCAC-UTSM-2010-10 Troubleshooting 6. E5 malfunction E5 display Voltage protection of compressor Check the voltage of outdoor unit power supply, whether the voltage Check the power supply between L(1) and N is about 172-265V Replace the power board, then check whether the system can run normally Trouble is solved Replace outdoor main board 7.
Page 120
Troubleshooting MLCAC-UTSM-2010-10 8. P1 malfunction P1 display High pressure protection Judge 1: Whether the wiring between the high pressure switch and main Connect it well control board is connected well or correctly Judge 2: Whether the high pressure switch is broken Method: Short connect the high pressure switch socket, check Replace high pressure switch whether the system can run normally...
Page 121
MLCAC-UTSM-2010-10 Troubleshooting 9. P2 malfunction P2 display Low pressure protection Judge 1: The wiring between the low pressure switch and main control board is connected well or correctly Connect it well Judge 2: Whether the low pressure switch is broken Method: Short connect the low pressure switch socket, check Replace low pressure switch whether the system can run normally...
Page 122
Troubleshooting MLCAC-UTSM-2010-10 10. P3 malfunction P3 display Current protection of compressor Judge 1: Check whether the input current of the power supply wire is more than 20A (For 36K & 48K with 1 phase, it is 30A) Check whether the refrigerant system is ok Judge 2: Check whether the outdoor ambient temperature is too high Stop the unit Make the outdoor unit ventilate well...
Page 123
MLCAC-UTSM-2010-10 Troubleshooting 11. P4 malfunction When compressor discharge temperature is higher than 115°C, the unit will stop, and unit runs again when compressor discharge temperature is lower than 90°C. P4 display Discharge temperature protection of compressor Check whether the compressor discharge temp. is more than 115°C ? Check whether the wiring connection is right between compressor discharge temp.
Page 124
Troubleshooting MLCAC-UTSM-2010-10 12. P5 malfunction When condenser high temp. is more than 65°C, the unit will stop, and unit runs again when outdoor pipe temp. less than 52°C. P5 display High temperature protection of condenser Check whether the condenser temperature is more than 65°C Check whether the resistance of condenser temp.
Page 125
MLCAC-UTSM-2010-10 Troubleshooting 13. P6 malfunction (For single phase units) P6 display Module protection Check whether the voltage range of P-N on IPM module is normal? DC277-356V for Regulate it to correct, 18K/24K/30KBtu/h; DC277-410V for then check whether the 36K/48KBtu/h Check whether the input power supply system can work is correct? 220-240V, 1N, 50Hz normally?
Page 126
Troubleshooting MLCAC-UTSM-2010-10 14. P6 malfunction (For three phases units) P6 display Module protection Regulate it to correct, then check whether the Check whether the voltage range of P-N on Check whether the input power supply system can work IPM module is normal? DC 350-650V is correct? 380-415V, 3N, 50Hz normally? Check whether the connecting line...
Page 127
MLCAC-UTSM-2010-10 Troubleshooting Appendix Indoor Temp. and Pipe Temp. Sensor Resistance Value Table (℃--K) ℃ ℃ ℃ ℃ K Ohm K Ohm K Ohm K Ohm 115.266 12.6431 2.35774 0.62973 108.146 12.0561 2.27249 0.61148 101.517 11.5000 2.19073 0.59386 96.3423 10.9731 2.11241 0.57683 89.5865 10.4736...
MLCAC-UTSM-2010-10 Precaution on Installation 1. Precaution on Installation 1). Measure the necessary length of the connecting pipe, and make it by the following way. Connect the indoor unit at first, then the outdoor unit. Bend the tubing in proper way. Do not harm them. Specially Notice the pipe length/height/dimension of each capacity.
Vacuum Dry and Leakage Checking MLCAC-UTSM-2010-10 2. Vacuum Dry and Leakage Checking Vacuum Dry: use vacuum pump to change the moisture (liquid) into steam (gas) in the pipe and discharge it out of the pipe to make the ℃. Use vacu pipe dry.
Page 131
MLCAC-UTSM-2010-10 Vacuum Dry and Leakage Checking ② . Special vacuum dry procedure This vacuum dry method is used in the following conditions: There’s moisture when flushing the refrigerant pipe. Rainwater may enter into the pipe. Vacuum dry for the first time ······ 2h pumping ③.
Additional Refrigerant Charge MLCAC-UTSM-2010-10 3. Additional Refrigerant Charge Caution Refrigerant cannot be charged until field wiring has been completed. b) Refrigerant may only be charged after performing the leak test and the vacuum pumping. When charging a system, care shall be taken that its maximum permissible charge is never exceeded, in view of the danger of liquid hammer.
MLCAC-UTSM-2010-10 Water Drainage 4. Water Drainage 4.1 Gradient and Supporting 1). Keep the drainpipe sloping downwards at a gradient of at least 1/50. Keep the drainpipe as short as possible and eliminate the air bubble. 2). The horizontal drainpipe should be short. When the pipe is too long, a prop stand must be installed to keep the gradient of 1/50 and prevent bending.
Water Drainage MLCAC-UTSM-2010-10 For Four-way cassette 4.4 Convergent drainage 1). The number of indoor units should be as small as possible to prevent the traverse main pipe overlong. 2). Indoor unit with drain pump and indoor unit without drain pump should be in different drainage system. 3).
Page 135
MLCAC-UTSM-2010-10 Water Drainage ③ Stop the air condi t ioner running, turn off the power, and put back the cover. Stop the air conditioner. After 3 minutes, check if it has abnormity. If the collocation of drainpipes is illogical, the water will flow back overfull, which will cause the alarm lamp flashes, even overflow from the water receipt plate.
Insulation Work MLCAC-UTSM-2010-10 5. Insulation Work 5.1 Insulation material and thickness 1). Insulation material ℃ in the high Insulation material should adopt the material which is able to endure the pipe’s temperature: no less than 70 -pressure side, no ℃ in the low less than 120 -pressure side(For the cooling type machine, no requirements at the low-pressure side.) ℃)
MLCAC-UTSM-2010-10 Insulation Work For construction convenience, before laying pipes, use insulation material to insulate the pipes to be deal with, at the same time, at two ends of the pipe, remain some length not to be insulated, in order to be welded and check the leakage after laying the pipes. 3).
Test Operation MLCAC-UTSM-2010-10 7. Test Operation (1) The test operation must be carried out after the entire installation has been completed. (2) Please confirm the following points before the test operation. The indoor unit and outdoor unit are installed properly. ...
Wireless Remote Controller MLCAC-UTSM-2010-10 1. Wireless Remote Controller 1.1 R11-HG/E Mode select button I/O Button Push the button to start Each time you push button, a mode is operation, push the selected in a sequence button again to stop that goes from AUTO, operation.
Page 141
MLCAC-UTSM-2010-10 Wireless Remote Controller 1.2 R05/BGE The R05/BGE wireless remote controller is for Four-way cassette type and the Ceiling& floor type. Mo de s etting Fan s peed se tti n g Adj us t Ad jus t MOD E S P EED Ai r dire ct i on setting ON/OFF...
Page 142
Wireless Remote Controller MLCAC-UTSM-2010-10 Buttons and functions 1. MODE: Once pressing, running mode will be selected in the following sequence: AUTO COOL HEAT FAN NOTE: No heating mode for cool only type unit. 2. FAN SPEED: Fan speed will be selected in following sequence once pressing this button: AUTO LOW HIGH : Decrease the set temp.
Page 143
MLCAC-UTSM-2010-10 Wireless Remote Controller 1.3 R51/CE The R51/CE wireless remote controller is only for MCA1-18CR. Remote Controller Specifications Model R51/CE Rated Voltage 3.0V Lowest Voltage of CPU Emitting Signal 2.0V Reaching Distance 8m (when using 3.0 voltage, it can get 11m) -5 ℃...
Page 144
Wireless Remote Controller MLCAC-UTSM-2010-10 10. FAN SPEED Button: This button is used for setting fan speed in the sequence that goes from AUTO, LOW, MED to HIGH, and then back to Auto. 11. TEMP UP Button: Push this button to increase the indoor temperature setting or to adjust the timer in a counter-clockwise direction.