7.4.
Automatic Mode Operation
Standard for Determining Operation Mode
• Indoor fan operates at SLo fan speed for 20 seconds.
• After judging indoor air temperature, the operation mode is determined and operation continued at the mode determined.
• After the operation mode has been determined, the mode does not change. However, Soft Dry mode operation includes
Cooling mode operation.
• Room temperature adjustment.
The following are added to the setting temperature specified as above.
• The mode judging temperature and standard setting temperature can be increased by 2°C, by open the circuit of JX6 at indoor
electronic controller.
7.5.
Sleep Mode Auto Operation
Cooling or Soft Dry Operation
Purpose is to obtain a comfortable room temperature while
sleeping. When you press the SLEEP Mode, the following
movement will start to avoid overcooling.
• Sleep shift operation starts, when the room temperature
reaches the setting temperature or after 1 hour of operation.
• The setting temperature will be risen by 0.5°C at the start of
operation and by 0.5°C one hour later.
• The airflow volume will automatically change to Lo- fan
speed.
• Sleep Mode operation time is 8 hours, the operation will be
stop after 8 hours.
• When used together with the Timer, the Timer has priority.