Summary of electrical connections
Note
The plugs are in the control unit pack.
Additional set value at plug aVF
External connections at plug aVD
When connecting external switching contacts or components to the protective
low voltage of the control unit, observe the requirements of protection class III,
i.e. 8.0 mm air gap/creepage path or 2.0 mm insulation thickness towards 'live'
components.
(cont.)
The 0-10 V hook-up provides an addi-
tional set boiler water temperature:
≙ 10 °C
1 V–
≙ 100 °C
10 V–
0 - 1 V– evaluated as "no default".
Connection to terminals "2" and "3" in
plug aVF.
25