SERVICE AND TECHNICAL SUPPORT MANUAL
igniter glows when inducer motor is disconnected,
shut down furnace immediately.
e. Determine reason pressure switch did not function
properly and correct condition.
f. Turn off 115−V power to furnace.
g. Reconnect inducer motor wires, replace outer door,
and turn on 115−V power.
h. Blower will run for 90 seconds before beginning the
call for heat again.
i. Furnace should ignite normally.

Checklist

1. Put away tools and instruments. Clean up debris.
2. Verify that the jumper is removed from the TEST/TWIN
terminal. Verify that there is nothing plugged into the PLT
connector.
NOTE: Note: If there is a jumper connector plugged into PLT,
remove it and discard. (See Figure 14)
3. Verify that Heating Operating Mode switch SW−1 is set
properly.. (See Figure 14)
4. Verify that the Blower/Heat Off−Delay SW−2 and SW−3
switches are set as desired. (See Figure 14)
5. Verify that the blower (lower door in upflow position) and
control ("Main" or upper door in upflow position) doors
are properly installed.
6. Verify that the Status LED glows. If not, check that the
power supply is energized and that the blower door is
secure. (See Figure 14) to interpret diagnostic codes.
7. Cycle test furnace with room thermostat to be sure that it
operates properly with the room thermostat. Check all
modes including Heat, Cool and Fan.
8. Check operation of accessories per manufacturer's
instructions.
9. Review Home Owner's Information with owner.
10. Attach entire literature packet to furnace.
SERVICE AND MAINTENANCE
PROCEDURES
Untrained personnel can perform basic maintenance functions
such as cleaning and replacing air filters. All other operations
must be performed by trained service personnel. A qualified
service person should inspect the furnace once a year.
WARNING
!
FIRE, INJURY OR DEATH HAZARD
Failure to follow this warning could result in personal
injury, death and/or property damage.
The ability to properly perform maintenance on this
equipment requires certain knowledge, mechanical
skills, tools, and equipment. If you do not possess
these, do not attempt to perform any service and
maintenance on this equipment other than those
procedures recommended in the Owner's Manual.
CAUTION
!
ENVIRONMENTAL HAZARD
Failure to
follow
this
environmental pollution.
Remove and recycle all components or materials (i.e.
oil, refrigerant, control board, etc.) before unit final
disposal.
440 04 4321 08
caution
may
result in
Specifications subject to change without notice.
WARNING
!
ELECTRICAL SHOCK, FIRE OR EXPLOSION
HAZARD
Failure to follow this warning could result in personal
injury or death, or property damage.
Before installing, modifying, or servicing system, main
electrical disconnect switch must be in the OFF
position and install a lockout tag. There may be more
than one disconnect switch. Lock out and tag switch
with a suitable warning label. Verify proper operation
after servicing.
CAUTION
!
ELECTRICAL OPERATION HAZARD
Failure to follow this caution may result in improper
furnace operation or failure of furnace.
Label all wires prior to disconnection when servicing
controls. Wiring errors can cause improper and
dangerous operation.
General
These instructions are written as if the furnace is installed in an
upflow application. An upflow furnace application is where the
blower is located below the combustion and controls section of
the furnace, and conditioned air is discharged upward. Since
this furnace can be installed in any of the 4 positions shown in
Figure 6, you must revise your orientation to component
location accordingly.
Figure 6
Multipoise Orientations

Electrical Controls and Wiring

Pressure Switches
Each pressure switch is labeled with the reference location
(noted as "COLLECTOR BOX−LPS" or "HOUSING−HPS" ON
THE SWITCH). The nominal break point of each switch is
shown on the label below the reference location in inches of
water column, "W.C." The maximum and minimum break point
of the switch is +/− 0.05 inches of water column from the
nominal break point of the switch. The maximum make point of
the switch is 0.10 inches of water above the maximum break
point of the switch
Example: Nominal break point on pressure switch is 0.68−in.
W.C. The minimum break point of the switch is 0.63−in. W.C.
The maximum break point of the switch is 0.73−in. W.C. The
maximum make point of the switch is 0.83−in. W.C.
Gas Furnace: (F/G)9MXT