System Heating Performance Data (Cont.)
Ducted Split System
53QDMT24-718
220-240V/1Ph/50Hz
Indoor Conditions
ESP
Fan
Flow
in.wg
Speed
High
0.20
Medium
in.wg
Low
High
0.24
Medium
in.wg
Low
Heat Pump
24/18°C DB/WB
Air
Temp. °C
Capacity
DB
cfm
Btu/hr
15°C
26665
580
20°C
25755
27°C
24125
15°C
25335
500
20°C
24470
27°C
22920
15°C
23055
188
20°C
22270
27°C
20860
15°C
26165
545
20°C
25270
27°C
23670
15°C
24860
465
20°C
24010
27°C
22490
15°C
22620
141
20°C
21850
27°C
20465
42QDMT24-718
Outdoor Ambient Temperature
7/6°C DB/WB
Input
Capacity
W
Btu/hr
2245
21455
2450
20430
2595
19200
2160
20385
2355
19410
2495
18240
1985
18550
2165
17665
2295
16600
2235
21050
2440
20045
2585
18840
2150
20000
2345
19045
2485
17900
1975
18200
2160
17330
2285
16290
71
38QDMT24-718
2/1°C DB/WB
Input
Capacity
W
Btu/hr
1930
17590
2070
16565
2235
15545
1855
16715
1990
15740
2150
14770
1705
15210
1830
14325
1975
13440
1920
17260
2060
16250
2225
15250
1845
16400
1980
15440
2140
14490
1700
14925
1820
14050
1970
13185
Input
W
1670
1825
1975
1605
1755
1900
1475
1615
1745
1665
1815
1965
1600
1745
1890
1475
1605
1740