Four-Lead Reconnectable (Single-Phase) Generator Sets Where Generator
Output Can Be Reconnected For 120 volt or 120/240 volt, 60 Hz,
When a generator set is reconnected to a voltage
different than nameplate voltage, notice should be
placed on the unit indicating this change. Decals for this
purpose
are
available
dealers/distributors.
120- or 110-Volt 3-Wire 2-Pole
Configuration--Figure 5-4
Jumper lead to be placed on line side of circuit breaker.
Leads L1 and L2 can either be left as separate leads or
can be connected together depending upon which is
practical for the given application. Regardless of the
number of phase (black) leads used in the application,
both circuit breakers must have leads attached to the
load side. It is recommended that jumper lead be
maintained for all straight 120- or 110-volt systems since
it helps balance the load of the generator set.
LO (Neutral)
Ground
4
3
2
1
Stator Leads
L0--L1
L0--L2
Figure 5-4. With Jumper Lead
5-4 Wiring Diagrams
110 volt or 110/220 volt, 50 Hz
NOTE
from
authorized
LO
GRD.
L2
L1
Load Side
Circuit
Breaker
Line Side
Jumper
Lead
60 Hz
50 Hz
120 volt
110 volt
120 volt
110 volt
120- or 110- Volt 2-Wire Configuration
If the installation requires a 120 or 110 volt, 2-wire
system, a single-pole circuit breaker must be used. See
Kohler
Figure 5-5. When connecting stator phase leads
together, the output lead (L1) must be sized accordingly.
Stator Leads
4
3
L0--L1
Figure 5-5 (Single Pole)
2
1
Line
Side
Load
Side
Ground
LO (Neutral)
60 Hz
100-120 volt
Figure 5-5. 120 Volt, 2-Wire
1-Pole
Circuit
Breaker
L1
GRD.
LO
50 Hz
100-120 volt
TP-5695 12/93