Buderus Logano G234X Installation And Maintenance Instructions Manual page 16

Gas-fired boiler
Hide thumbs Also See for Logano G234X:
Table of Contents

Advertisement

5
Installing the boiler
B Mount the Logamatic sensor well [2] on the boiler
instead of the temperature/pressure gauge and seal.
B Place the Logamatic sensor packet [1] under the front
boiler cover towards the front for the sensor well.
Fig. 16 Mounting the Logamatic sensor well on the
boiler
1
Logamatic sensor packet
2
Logamatic sensor well
3
Logamatic 2000 control unit
B Place entire Logamatic sensor packet fully into the
immersion well [1] to the stop.
The plastic coil [2] is pushed back automatically.
B At the same time insert the compensating spring [3]
into the sensor well [1].
B Press sensor clip [5] (scope of delivery of the control
unit) from the side or from above to the head of the
sensor well.
B Carefully roll up unnecessary wiring and capillaries and
stow in the Logamatic 2000 control unit.
Fig. 17 Sensor well and temperature sensor
1
Sensor well
2
Plastic coil
3
Compensator spring
4
Capillary line
5
Sensor retaining clip
16
Power connection and connections of additional
components
B Establish a permanent connection to the control unit in
accordance with the locally applicable regulations.
B Route all wiring to the control unit through the conduit
and connect as specified by the control unit circuit
diagram.
Installing strain relief
The required cable clips are in the scope of delivery of the
control unit.
Insert the cable clip together with the cable from the top
into the slots in the frame. The bar of the lever must point
upwards.
Slide the cable clip downwards.
Counterhold.
Flip the lever up.
Fig. 18 Installing strain relief
Logano G234X - Technical specifications are subject to change without prior notice.
DANGER: Fire hazard from hot boiler
components!
Hot boiler components may damage
electrical cables.
B Ensure that the electrical cables are not
touching any hot parts.
B Make sure that all cables are routed
through the conduits provided or on the
outside of the boiler's thermal insulation.