Amana xMVM97 series Installation Instructions Manual page 13

Modulating gas furnace
Table of Contents

Advertisement

D
T
L
RAIN
RAP AND
INES
In horizontal applications the condensate drain trap is secured to
the furnace side panel, suspending it below the furnace. A mini-
mum clearance of 5 1/2 inches below the furnace must be pro-
vided for the drain trap. Additionally, the appropriate downward
piping slope must be maintained from the drain trap to the drain
location. Refer to Condensate Drain Trap and Lines for further
details. If the drain trap and drain line will be exposed to tem-
peratures near or below freezing, adequate measures must be
taken to prevent condensate from freezing.
L
EVELING
Leveling ensures proper condensate drainage from the heat ex-
changer and induced draft blower. For proper flue pipe drainage,
the furnace must be level lengthwise from end to end. The
furnace should have a slight tilt from back to front with the
access doors downhill from the back panel approximately 1/2
to 3/4 inches. The slight tilt allows the heat exchanger conden-
sate, generated in the recuperator coil, to flow forward to the
recuperator coil front cover.
A
E
LTERNATE
LECTRICAL AND
This furnace has provisions allowing for electrical and gas line
connections through either side panel. In horizontal applications
the connections can be made either through the "top" or "bot-
tom" of the furnace.
D
P
RAIN
AN
A drain pan must be provided if the furnace is installed above a
conditioned area. The drain pan must cover the entire area
under the furnace (and air conditioning coil if applicable).
F
P
REEZE
ROTECTION
Refer to Horizontal Applications and Conditions - Drain Trap and
Lines.
P
G
/H
A
ROPANE
AS
IGH
P
OSSIBLE PROPERTY DAMAGE
OCCUR IF THE CORRECT CONVERSION KITS ARE NOT INSTALLED
APPROPRIATE KITS MUST BE APPLIED TO ENSURE SAFE AND PROPER
. A
FURNACE OPERATION
LL CONVERSIONS MUST BE PERFORMED BY A
QUALIFIED INSTALLER OR SERVICE AGENCY
This furnace is shipped from the factory configured for natural
gas up to 10,000 ft. altitude. Propane conversions require
the proper LP kit to compensate for the energy content dif-
ference between natural and propane gas.
G
L
C
AS
INE
ONNECTIONS
I
L TITUDE
NSTALLATIONS
WARNING
,
PERSONAL INJURY OR DEATH MAY
.
Gas
A ltitude
Natural
0-10,000
Propane
N O T E : In Canada, gas furnaces are o nly certified to 4500 feet.
For furnaces being converted to LP gas, it is strongly recom-
mended that a LPLP03 kit also be installed. The use of this
kit will prevent the furnace from firing when the LP gas sup-
ply pressure is too low to support proper combustion.
The indicated kit must be used to ensure safe and proper fur-
nace operation. All conversions must be performed by a quali-
fied installer, or service agency.
V
/F
ENT
LUE
F
AILURE TO FOLLOW THESE INSTRUCTIONS CAN RESULT IN BODILY
INJURY OR DEATH
GIVEN IN THIS SECTION
U
PON COMPLETION OF THE FURNACE INSTALLATION
INSPECT THE ENTIRE FLUE SYSTEM BOTH INSIDE AND OUTSIDE OF THE
FURNACE TO ASSURE IT IS PROPERLY SEALED
SYSTEM CAN RESULT IN SERIOUS PERSONAL INJURY OR DEATH DUE TO
EXPOSURE TO FLUE PRODUCTS
A condensing gas furnace achieves its high level of efficiency by
extracting almost all of the heat from the products of combus-
tion and cooling them to the point where condensation takes
place. Because of the relatively low flue gas temperature and
water condensation requirements, PVC or ABS pipe is used as
venting material.
In addition to PVC and ABS pipe and fittings, Innoflue
Centrotherm Eco Systems and PolyPro
also approved vent and combustion air materials for instal-
. T
HE
lations in the U.S.A. and Canada. Manufacturers Installation
instructions for these products must be followed. These prod-
ucts have specific instructions for installing, joining and
terminating. Do not mix materials or components of one
manufacturer with materials or components of another manu-
facturer.
All furnaces are built with 2" vent / intake pipe and connec-
tors. For furnaces requiring installation of 3" pipe, the tran-
sition from 2" to 3" should be done as close to the furnace as
practically possible.
Manifold Pressure
Kit
Orific e
High
Stage
1
None
#45
3.5" w.c.
2
LPM-09 1.25MM
10.0" w.c.
P
& C
A
IPE
OMBUSTION
WARNING
. C
AREFULLY READ AND FOLLOW ALL INSTRUCTIONS
.
WARNING
. L
EAKS IN THE FLUE
,
INCLUDING CARBON MONOXIDE
by M&G Duravent are
®
Pressure
Low Stage
Sw itc h
(50% firing
Change
rate)
1" w.c.
None
2.6" w.c.
None
P
IR
IPE
,
CAREFULLY
.
by
®
13