4.3.6 Check the vent damper

WARNING: Risk of life from leaking flue gases.
▶ Check that the flue gas damper operates properly.
▶ Check the flue gas damper position. The flap must be fully opened
(vertical position). No flue gas must escape from the draft hood when
the burner is operating.
4
3
2
1
Fig. 15 Checking the flue gas damper
[1]
Open draft hood
[2]
Flue gas connection
[3]
Flue gas damper
[4]
Flue gas damper position indicator
[5]
Flue gas flap motor
[6]
Flue gas collector
[7]
Boiler
12

4.3.7 Checking the AquaSmart

Check operation of the maximum setting on the AquaSmart to make sure
that the boiler switches off as soon as the boiler water temperature set
on the AquaSmart is reached. Record the result in the commissioning
report.
▶ Adjust the setting on the AquaSmart to the desired value.
▶ Replace the front door and close it.
5
6
7
6 720 804 435-14.1T
Fig. 16 Check temperature controller
[1]
▶ Install boiler front panel.
Fig. 17 Installing the boiler front panel
[1]
[2]
[3]
Adjustment keypad
Locking screws
Boiler jacket
Boiler front panel
Logano G234X – 6 720 805 917 (2012/12)